Notes | General Note: LABS release â in accordance with test specification VWPV3.10.7:2005-0 When connecting the conductor, make sure that the CAPAROC modules are not pulled apart due to tensile force. Gaps must not be created between the modules. Observe the specified conditions for use in potentially explosive areas. Install the device in a suitable approved housing with at least IP54 degree of protection that meets the requirements of IEC/EN60079-0. Also observe the requirements of IEC/EN60079-14.
|
Product properties | Type: Plug-in module Product type: Device circuit breakers Product family: CAPAROC Number of positions: 1 No. of channels: 2 Number of slots: 2 Insulation characteristics Protection class: III Pollution degree: 2
|
Electrical properties | No. of channels: 2 General Operating voltage: 10 VDC ... 30 VDC Rated voltage: 12 VDC 24 VDC Rated current IN: 10 ADC (per channel) 2/4/6/8/10ADC(Adjustable via rotary coding switches) 1/2/3/4/5/6/7/8/9/10ADC(can be set, in RC mode via power module with communication interface) Rated current (pre-adjusted): 2 A Rated surge voltage: 0.5 kV Tripping method: E (electronic) Feedback resistance: max. 35 VDC Switch-on delay: 50 ms (each channel preset by default) can be adapted with CAPAROC PMIOL and CAPAROC PMPN power modules Required backup fuse: Only required if Imax of the power supply > the short-circuit switching capacity. Integrated failsafe element. Short-circuit switching capacity: 300 A Dielectric strength: 35 VDC (Load circuit) Active current limitation: typ. 2.0x IN at IN ⤠3A typ. 1.5x IN at IN ⥠4A Fuse: electronic Efficiency: > 99 % Closed circuit current I0: typ. 25 mA (no load at 24V) Power dissipation: typ. 0.6 W (no load at 24V) < 3.3 W (in nominal operation at 24V and 10A) Measuring tolerance I: ± 10 % (typ.) Temperature derating: 20 A (Total current at40°C) 10 A (Total current at 65°C) MTBF (IEC 61709, SN 29500): 11140621 h (at 25°C with 21% load) 4699883 h (at40°C with 34.25%load) 534110 h (at40°C with 100%load) Voltage drop: 0.14 V (at 10 A) Fail-safe element: 15 ADC (per output channel) Load circuit Shutdown time: 5 s (for overload 1.1â¦1.3xIN at IN ⥠4A) 5 s (for overload 1.1â¦1.7xIN at IN < 4A) typ. 400 ms (max. 450ms for high starting currents) typ. 20 ms (for short circuit > 1,5 x IN) Undervoltage switch-off: ⤠8.5 VDC (active) ⥠9.2 VDC (inactive) Overvoltage switch-off: ⥠32.5 VDC (active) ⤠30.5 VDC (inactive) Max. capacitive load: ⤠75000 µF (Depending on the current setting and the short-circuit current available)
|
Connection data | Fuse-protected output Connection method: Push-in connection Stripping length: 10 mm Conductor cross section flexible: 0.2 mm² ... 4 mm² Conductor cross section rigid: 0.2 mm² ... 4 mm² Conductor cross section AWG: 24 ... 12 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 4 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 4 mm²
|
Signaling | Channel LED off: off (Channel switched off) Channel LED yellow: lit (Channel switched on, channel load>80%) two flashes (Check the installation, no communication to power module) Channel LED green: lit (Channel switched on) flashing (Channel switched on, coding switch position is not equal to set value) Channel LED red: lit (Channel switched off, over- or undervoltage active) ON temporarily (Channel switched off, 5s cool-down phase, overload or short-circuit release) flashing (Channel switched off, ready to be switched back on, overload or short-circuit release) two flashes (Channel switched off, system total current limit exceeded) Channel LED red-yellow: flashing (Channel is overloaded and is switched off) Channel LED red-green: flashing (Channel switched off, programming mode active, current adjustment after overload or short-circuit release)
|
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/b0f91290c277b94ba6f21ceffa4d4ef8/-S204x204-FJPG Width: 12.4 mm Height: 132.4 mm Depth: 111.3 mm (incl. DIN rail 7.5mm)
|
Material specifications | Material: PA 6 PC Flammability rating according to UL 94: V-0
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -30°C ... 65°C (The temperature range of the power module must be taken into consideration) Ambient temperature (storage/transport): -40°C ... 70°C Altitude: ⤠4000 m (amsl) Humidity test: 96h, 95%RH, 40°C Shock (operation): 30g (11 ms period, half-sine shock pulse, according to IEC 60068-2-27) 25g (6ms duration, half-sine shock pulse in accordance with IEC 60068-2-27, continuous shock) Vibration (operation): 5g (10 ... 150Hz / 10cycles / axis / X,Y,Z)
|
Approvals | UL approval Identification: UL/C-UL Listed UL 508 UL Recognized UL 2367 UL 121201 Class I, Division 2, Groups A, B, C, D, T4A ATEX Identification: TÃV22 ATEX8874 X II 3G Ex ec IIC T4 Gc IECEx Identification: IECExTUR22.0049X II 3G Ex ec IIC T4 Gc UKCAEx(UKEX) Identification: TÃV22UKEX7109X II 3G Ex ec IIC T4 Gc
|
Standards and regulations | Standards/specifications: EN61000-6-2 EN61000-6-3 EN60068-2-78 EN50178 EN60068-2-6 EN60068-2-27 IEC 60079-7 IEC 60079-0 Note: EMC â Immunity for industrial areas EMC â Emission for residential, business and commercial properties and small operations Environmental influences â Moisture and heat, constant Equipping power installations with electronic equipment Environmental influences â Vibrations (sinusoidal) Environmental influences â Shocks Explosive atmospheres â Part7: Equipment protection by increased safety âeâ Explosive atmospheres â Part0: Equipment â General requirements
|
Mounting | Mounting type: pluggable onto CAPAROC CR⦠current rail
|