Automazione Industriale

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Software di progettazione

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 2320898
PHOENIX CONTACTNon disponibile

QUINT-PS/1AC/24DC/20/CO - Power supply, with protective coating

Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, SFB Technology (Selective Fuse Breaking), input:1-phase, output: 24 VDC / 20 A
Cod. Articolo: 2320898
Cod. Fornitore: 2320898
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Input dataAC operation
Nominal input voltage range: 100 VAC ... 240 VAC
110 VDC ... 250 VDC
Input voltage range: 85 VAC ... 264 VAC
90 VDC ... 410 VDC +5% (UL 508: ≤ 250 V DC)
Input voltage range AC: 85 VAC ... 264 VAC
Input voltage range DC: 90 VDC ... 410 VDC +5% (UL 508: ≤ 250 V DC)
Electric strength, max.: 300 VAC
Voltage type of supply voltage: AC/DC
Inrush current: < 20 A
Inrush current integral (I2t): < 3.2 A2s
AC frequency range: 45 Hz ... 65 Hz
Frequency range DC: 0 Hz
Mains buffering time: typ. 32 ms (120VAC)
typ. 32 ms (230 V AC)
Current consumption: 7 A (100VAC)
3.1 A (240VAC)
5.1 A (120VAC)
2.3 A (230 V AC)
4.9 A (110VDC)
2.4 A (220 VDC)
6.3 A (110VDC)
2.7 A (250VDC)
Nominal power consumption: 569 VA
Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester
Typical response time: < 0.6 s
Input fuse: 12 A (slow-blow, internal)
Permissible backup fuse: B10 B16 AC:
Permissible DC backup fuse: DC: Connect a suitable fuse upstream
Recommended breaker for input protection: 10 A ... 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: > 93 % (230 V AC)
Nominal output voltage: 24 VDC ±1%
Setting range of the output voltage (USet): 18 VDC ... 29.5 VDC (> 24 VDC, constant capacity restricted)
Nominal output current (IN): 20 A (-25°C...60°C, UOUT =24VDC)
POWER BOOST (IBoost): 26 A (-25°C...40°C permanent, UOUT = 24VDC )
Selective Fuse Breaking (ISFB): 120 A (12ms)
Magnetic circuit breaker tripping: B2 / B4 / B6 / B10 / B16 / C2 / C4 / C6
Derating: 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: ≤ 35 VDC
Protection against overvoltage at the output (OVP): < 32 VDC
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 2 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 30 mVPP (with nominal values)
Output power: 480 W
Maximum no-load power dissipation: 8 W
Power loss nominal load max.: 40 W
Rise time: < 0.1 s (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK active
Output description: UOUT > 0.9 x UN: High signal
Switching voltage range: 18 VDC ... 24 VDC
Maximum inrush current: 20 mA (short-circuit-proof)
Continuous load current: ≤ 20 mA
Signal: DC OK floating
Output description: Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage: 30 VAC
24 VDC
Maximum inrush current: 0.5 A
1 A
Continuous load current: ≤ 1 A
Signal: POWER BOOST, active
Output description: IOUT < IN: High signal
Switching voltage range: 18 VDC ... 24 VDC
Output voltage: + 24 VDC
Maximum inrush current: 20 mA (short-circuit-proof)
Continuous load current: ≤ 20 mA
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Conductor cross section AWG min.: 18
Conductor cross section AWG max.: 10
Stripping length: 7 mm
Screw thread: M4
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Conductor cross section AWG min.: 12
Conductor cross section AWG max.: 10
Stripping length: 7 mm
Screw thread: M4
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Conductor cross section AWG min.: 18
Conductor cross section AWG max.: 10
Screw thread: M4
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Active switching output
Relay contact
Signal output: DC OK active
Status display: UOUT > 0.9 x UN: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED
IOUT < IN: LED ON
LED flashing
Color: green
Signal output: DC OK floating
Status display: UOUT > 0.9 x UN: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED
LED flashing
Color: green
Signal output: POWER BOOST, active
Status display: IOUT > IN: LED "BOOST" yellow
Color: yellow
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 500 VDC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 900000 h (25°C)
> 520000 h (40°C)
Insulation characteristics
Protection class: I
Degree of pollution: 2
DimensionsWidth: 90 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
Alternative assembly
Width: 122 mm
Height: 130 mm
Depth: 93 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: PN ≥50%, 5mm horizontally, 15mm next to active components, 50mm vertically
alignable: PN <50%, 0mm horizontally, 40mm vertically top, 20 mm vertically bottom
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: yes
Material specificationsHousing material: Metal
Hood version: Galvanized sheet steel, free from chrome (VI)
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Maximum altitude: 6000 m
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): 100 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsRail applications: EN50121-4
EN50121-3-2
HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard - Electrical safety: IEC 61010-2-201(SELV)
Explosive atmosphere: EN60079-15 (Zone2)
Standard - Equipment safety: BG (design tested)
Standard – Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Noxious gas test: ISA-S71.04-1985 G3 Harsh Group A
Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMI F47-0706 Compliance Certificate
DeviceNet approval: DeviceNet™ Power Supply Conformance Tested
Overvoltage category
EN 62477-1: III
ApprovalsCSA: CAN/CSA-C22.2 No.60950-1-07
CSA-C22.2 No.107.1-01
Shipbuilding approval: DNVGL(EMCB, only with upstream filter)
SIQ: BG (type approved)
UL approvals: UL/C-UL listed UL508
UL/C-UL Recognized UL60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
DeviceNet approval: DeviceNet™ Power Supply Conformance Tested
Conformity/Approvals
ATEX: II3GExecicnCIICT4Gc
SIQ 14 ATEX 137 X
IECEx: Ex ec ic nC IIC T4 Gc
IECEx SIQ 14.0001X
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Noise emission: EN 55011 (EN 55022)
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Specifiche
ECLASSECLASS-11.0: 27040701
ECLASS-12.0: 27040701
ECLASS-13.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00041.pdf

Approvals_00054.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00149.pdf

Approvals_01206.pdf

Approvals_01302.pdf

Data_sheet_03124.pdf

Manufacturer_declaration_00623.pdf

Manufacturer_declaration_01301.pdf

Manufacturer_declaration_14320.pdf

Package_slip_02064.pdf

Product_information_00152.pdf

Technical_drawing_37416.pdf

Various_00080.pdf

Various_00006.pdf