AXL F UTH8 1F - Temperature module

AxiolineF, Temperature recording module, Analog inputs: 8 (8 inputs for thermocouples or linear voltage, plus 1 input -5V to +5V), connection technology: 2-conductor (shielded, twisted pair), transmission speed in the local bus: 100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connectors
Cod. Articolo: 2688417
Cod. Fornitore: 2688417
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3f783436b27c3846a361ee861b282789/-S204x204-FJPG
Width: 53.6 mm
Height: 126.1 mm
Depth: 54 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
InterfacesAxiolineFlocal bus
Number of interfaces: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
System propertiesModule
Input address area: 18 Byte
Output address area: 18 Byte
Required parameter data: 27 Byte (20bytes for configuration with GSD AXL UTH 8 (packed))
Required configuration data: 7 Byte
Input dataAnalog
Input name: Analog inputs
Description of the input: Inputs for thermocouples or linear voltage
Number of inputs: 8 + 1 (8 inputs for thermocouples or linear voltage, plus 1 input -5V to +5V)
Connection method: Push-in connection
Connection technology: 2-conductor (shielded, twisted pair)
A/D converter resolution: 24 bit
Sensor types (RTD) that can be used: Pt 100 (4 external cold junctions, can also be used as a sensor input)
Sensor types that can be used (TC): U, T, L, J, E, K, N, S, R, B, C, W, HK
Measuring principle: Sigma/Delta process
Measured value representation: 16 bits (15 bits + sign bit)
Input filter time: 40 ms
60 ms
100 ms
120 ms (adjustable)
Protective circuit: Short-circuit protection, overload protection of the inputs
Transient protection of inputs
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Mounting position: any (no temperature derating; Parameterize the mounting position using the object 0080hex ParaTable!)
Scope of delivery: including bus base module and AxiolineF connectors
Insulation characteristics
Overvoltage category: II (IEC 60664-1, EN60664-1)
Pollution degree: 2 (IEC 60664-1, EN60664-1)
Electrical propertiesPotentials
Power consumption: typ. 1.63 W (entire device)
max. 2.58 W (entire device)
Potentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Current draw: max. 180 mA
typ. 115 mA
Power consumption: max. 0.9 W
typ. 0.55 W
Potentials: Supply for analog modules (U
Supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 70 mA
typ. 45.3 mA
Power consumption: max. 1.68 W
Protective circuit: Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; Polarity protection diode
Transient protection; Suppressor diode
Electrical isolation/isolation of the voltage ranges
Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min.
Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: AxiolineF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
MountingMounting type: DIN rail mounting
Mounting position: any (no temperature derating; Parameterize the mounting position using the object 0080hex ParaTable!)
Specifiche
ECLASSECLASS-11.0: 27242601
ECLASS-12.0: 27242601
ECLASS-13.0: 27242601
ETIMETIM 9.0: EC001596
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01328.pdf

Approvals_01329.pdf

Approvals_01758.pdf

Data_sheet_03162.pdf

Manual_00006.pdf

Manual_00007.pdf

Manufacturer_declaration_00695.pdf

Manufacturer_declaration_01605.pdf

Manufacturer_declaration_05480.pdf

Manufacturer_declaration_05562.pdf

Manufacturer_declaration_05563.pdf

Manufacturer_declaration_14405.pdf

Package_slip_00772.pdf

Product_information_00033.pdf

Product_information_00245.pdf

Technical_drawing_37508.pdf

Various_00004.pdf