Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/b1c003a181894d4f8ddc9482edbf941e/-S204x204-FJPG Width: 60 mm Height: 185 mm Depth: 30.5 mm Drill hole spacing: 198.5 mm Note on dimensions: The height is 212 mm including fixing clips.
|
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
|
Material specifications | Housing material: Pocan® Color: anthracite
|
Interfaces | Ethernet Number of interfaces: 2 No. of channels: 2 Connection method: M12 fast connection technology Note on the connection method: D-coded Number of positions: 4 Transmission speed: 10/100 Mbps (with auto negotiation) Modbus/TCP Equipment type: Modbus slave (server) System-specific protocols: Modbus protocols Modbus/TCP Protocols supported: SNMP v1 HTTP TFTP FTP BootP DHCP Specification: Modbus application protocol V1.1b
|
Input data | Digital Input name: Digital inputs at pin 2 for class A ports Description of the input: IEC 61131-2 type 1 Number of inputs: 4 Connection method: M12 connector, X01 ... X04 have double occupancy Connection technology: 3-conductor Input voltage range "0" signal: -0.3 VDC ... 5 VDC Input voltage range "1" signal: 15 VDC ... 30 VDC Nominal input voltage UIN: 24 VDC Nominal input current at UIN: typ. 3 mA Sensor current per channel: max. 200 mA (from L+/L-) Total sensor current: max. 1.6 A (from L+/L-) Input frequency: 0.5 kHz Input filter time: < 1000 µs Protective circuit: Overload protection, short-circuit protection of sensor supply Digitalâ Description of the input: IO-Link ports in digital input (DI) mode Number of inputs: max. 8 (EN 61131-2 type 1) Connection method: M12 connector, X01 ... X04 have double occupancy Connection technology: 3-conductor Nominal input voltage UIN: 24 VDC Input voltage range "0" signal: -0.3 VDC ... 5 VDC Input voltage range "1" signal: 15 VDC ... 30 VDC Nominal input current: typ. 3 mA Sensor current per channel: max. 200 mA (from L+/L-) Total sensor current: max. 1.6 A (from L+/L-) Input filter time: < 1000 µs Input frequency: 0.5 kHz Protective circuit: Overload protection; yes Short-circuit protection for the sensor supply; yes IO-Link Number of ports: 4 Connection method: M12 fast connection technology Connection technology: 3-conductor Port type: Class A Cycle Time: min. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2") IO-Linkâ Number of ports: 4 Connection method: M12 fast connection technology Connection technology: 3-conductor Port type: Class B Cycle Time: min. 2 ms (MasterCycleTime: PDInput* + PDOutput* + OnReqData* < = 17 Bytes, COM3; * see "IO-Link Interface and System Specification V1.1.2")
|
Output data | Digital Output description: IO-Link ports in digital output (DO) mode Connection method: M12 connector, X01 ... X04 have double occupancy Connection technology: 3-conductor Number of outputs: max. 8 Nominal output voltage: 24 VDC Maximum output current per channel: 150 mA Maximum output current per module: 1.2 A Nominal load, ohmic: 3.6 W (160 é, at nominal load) Nominal load, inductive: 3.6 VA (0.8H, 160é, at nominal load) Signal delay: max. 150 µs (when switched on) max. 200 µs (when switched off) Switching rate: 1 per second, maximum (at nominal inductive load) 5500 per second, maximum (at nominal ohmic load) Limitation of the voltage induced on circuit interruption: -15 VDC Output voltage when switched off: max. 1 V Output current when switched off: max. 300 µA Protective circuit: Overload protection; yes Short-circuit protection; yes Behavior with overload: Shutdown with automatic restart
|
Product properties | Type: Stand-Alone Product type: I/O component Product family: AxiolineE
|
Electrical properties | Potentials Voltage supply US: 24 VDC Power supply at US: max. 4 A Current consumption from US: typ. 8 mA max. 1.2 A Supply: IO-Link Nominal voltage for I/O supply: 24 VDC Nominal current for every IO-Link port: max. 150 mA (at C/Q (pin 4), maximum of 1.6 A over all 8 IO-Link C/Q and L+ cables) max. 200 mA (at L+/L- (pin 1 and pin 3), during startup, up to 1.6 A for short periods) max. 2 A (at UA (IO-Link B ports, pin 2 and pin 5)) Permissible cable length: < 20 m Protective circuit: Overload protection; yes Supply: Module electronics and sensors Designation: Supply of module electronics and sensors (US) Connection method: M12 connector (T-coded) Number of positions: 4 Supply voltage: 24 VDC Supply voltage range: 19.5 VDC ... 31.2 VDC (including all tolerances, including ripple) Current consumption: typ. 180 mA ±15% (at 24 V DC) max. 12 A Supply: Actuators Designation: Supply of actuators (UA) Connection method: M12 connector (T-coded) Number of positions: 4 Supply voltage: 24 VDC Supply voltage range: 18 VDC ... 31.2 VDC (including all tolerances, including ripple) Current consumption: typ. 28 mA ±15% (at 24 V DC) max. 12 A Electrical isolation/isolation of the voltage ranges Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet1): 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/bus connection (Ethernet2): 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (communications power and sensor supply, IO-Link ports)/FE: 500 VAC, 50 Hz, 1 min. Test voltage: Bus connection (Ethernet1)/FE: 500 VAC, 50 Hz, 1 min. Test voltage: Bus connection (Ethernet2)/FE: 500 VAC, 50 Hz, 1 min. Test voltage: Bus connection (Ethernet1)/bus connection (Ethernet2): 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (actuator supply)/24 V supply (communications power and sensor supply, IO-Link ports): 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (actuator supply)/bus connection (Ethernet1): 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (actuator supply)/bus connection (Ethernet2): 500 VAC, 50 Hz, 1 min. Test voltage: 24 V supply (actuator supply)/FE: 500 VAC, 50 Hz, 1 min.
|
Connection data | Connection method: M12 connector
|
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP65/IP67 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -25°C ... 85°C Permissible humidity (operation): 5 % ... 95 % Permissible humidity (storage/transport): 5 % ... 95 %
|
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1)
|
Mounting | Mounting type: Wall mounting
|