Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/172c7c5767999646b422d3edebda44f8/-S204x204-FJPG Width: 35 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715).
|
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area
|
Interfaces | AxiolineÃFÃlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps
|
System properties | Module Input address area: 8 Byte Output address area: 8 Byte Required parameter data: 7 Byte Required configuration data: 6 Byte
|
Input data | Analog Input name: Analog inputs Description of the input: Differential inputs, voltage Number of inputs: 4 A/D conversion time: 31.25 õs A/D converter resolution: 16 bit Connection method: Push-in connection Connection technology: 2-, 3-, 4-conductor Note regarding the connection technology: shielded, twisted pair Voltage input signal: 0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V Input resistance of voltage input: 268 ké (typical) Data formats: IB IL, S7-compatible Input filter: 30 Hz, 12 kHz and mean-value generation (can be parameterized) Limit frequency (3 dB): 30 Hz 12 kHz Common mode voltage range signal - ground: -50 VÃDC ... 50 VÃDC Measured value representation: 16 bits (15 bits + sign bit) Protective circuit: Transient protection of inputs; Suppressor diode Overload protection of the voltage inputs; ñ30 V DC, maximum
|
Product properties | Type: block modular Product type: I/O component Product family: AxiolineÃF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineÃF connectors Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1)
|
Electrical properties | Potentials Power consumption: typ. 1.51 W (Device, total, plus the power consumption of the external sensors) max. 1.78 W (Device, total, plus the power consumption of the external sensors) Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Current draw: max. 150 mA typ. 120 mA Power consumption: max. 0.75 W typ. 0.6 W Potentials: Supply for analog modules (U Supply voltage: 24 VÃDC (I/O supply and sensor supply) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 245 mA (IiS = 4 x 50 mA (full load)) max. 45 mA (IiS = 0 mA) typ. 118 mA (IiS = 4 x 20 mA (nominal load)) max. 125 mA (IiS = 4 x 20 mA (nominal load)) typ. 238 mA (IiS = 4 x 50 mA (full load)) Power consumption: max. 5.88 W (Full load) Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; up to HWÃ02: polarity protection diodefrom HWÃ03: parallel diode; with external 5ÃA fuse (for startup only) Transient protection; Suppressor diode Supply: Designation: Sensor supply UiS Supply voltage: 24 VÃDC (from UA) Current consumption: max. 50 mA (per channel) Electrical isolation/isolation of the voltage ranges Test voltage: 5ÃV supply of the local bus (UBus) / 24ÃV supply (I/Os): 500 VÃAC, 50 Hz, 1 min. Test voltage: 5ÃV supply of the local bus (UBus)/analog inputs: 500 VÃAC, 50 Hz, 1 min. Test voltage: 5ÃV supply of the local bus (UBus) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24 V supply (I/O)/analog inputs: 500 VÃAC, 50 Hz, 1 min. Test voltage: 24ÃV supply (I/O) / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: Analog inputs/functional ground: 500 VÃAC, 50 Hz, 1 min.
|
Connection data | Connection technology Connection name: AxiolineÃF connector Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã
AxiolineÃF: system and installationâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã
AxiolineÃF: system and installationâ⬠user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm
|
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (Standard, applications with UL approval, use in zoneÃ2 potentially explosive area) -40°C ... 70°C (Extended, see section ââ¬Ã
Tested successfully: use under extreme ambient conditionsâ⬠in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
|
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1)
|
Approvals | ATEX Identification: ïà II 3 G Ex ec IIC T4 Gc Certificate: UL 20 ATEX 2441X UKEX Identification: ïà II 3 G Ex ec IIC T4 Gc Certificate: PxCIMA22UKEX2701949X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx ULD 20.0026X UL, USA/Canada Identification: cULus Certificate: E238705 UL Ex, USA / Canada Identification: Class I, Zone 2, AEx ec IIC T4 ClassÃI, DivisionÃ2, Groups A, B, C, D, T4 Ex ec IIC T4 Gc X Certificate: E366272 CCCÃ/ÃChina-Ex Identification: Ex ec IIC T4 Gc Certificate: ïì, 2021122309114456
|
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating)
|