Input data | AC operation Nominal input voltage range: 100 VÃAC ... 240 VÃAC 120 VÃDC ... 300 VÃDC (UL 508: ââ°¤ 250 V DC) Input voltage range: 85 VÃAC ... 264 VÃAC 90 VÃDC ... 300 VÃDC (UL 508: ââ°¤ 250 V DC) Input voltage range AC: 85 VÃAC ... 264 VÃAC Input voltage range DC: 90 VÃDC ... 300 VÃDC (UL 508: ââ°¤ 250 V DC) Electric strength, max.: 300 VÃAC Voltage type of supply voltage: AC/DC Inrush current: < 15 A (typical) Inrush current integral (I2t): < 1.6 A2s AC frequency range: 45 Hz ... 65 Hz Frequency range DC: 0 Hz Mains buffering time: typ. 20 ms (120ÃVÃAC) typ. 22 ms (230 V AC) Current consumption: 8.7 A (120ÃVÃAC) 4.5 A (230 V AC) 9.4 A (110ÃVÃDC) 4.6 A (220 VÃDC) Nominal power consumption: 1046 VA Protective circuit: Transient surge protection; Varistor Typical response time: < 0.65 s Input fuse: 20 A (fast blow, internal) Permissible backup fuse: B16 B25 AC: Permissible DC backup fuse: DC: Connect a suitable fuse upstream Recommended breaker for input protection: 6 A ... 16 A (AC: Characteristics B, C, D, K) Discharge current to PE: < 3.5 mA
|
Output data | Efficiency: > 93 % (for 230 V AC and nominal values) Nominal output voltage: 48 VÃDC ñ1Ã% Setting range of the output voltage (USet): 30 VÃDC ... 56 VÃDC (> 48ÃVÃDC, constant capacity restricted) Nominal output current (IN): 20 A (-25ðCÃ...Ã60ðC, UOUT = 48ÃVÃDC) POWER BOOST (IBoost): 22.5 A (-25ðCÃ...Ã40ðC permanent, UOUT = 48ÃVÃDC ) Selective Fuse Breaking (ISFB): 100 A (12Ãms) Magnetic circuit breaker tripping: B2 / B4 / B6 / B10 / C2 / C4 / C6 Derating: 60°C ... 70°C (2.5%/K) Feedback voltage resistance: max. 60 VÃDC Protection against overvoltage at the output (OVP): < 60 VÃDC Active current limitation: Approx. IBOOST = 22.5 A (for short-circuit) Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ñ10 %) Residual ripple: < 50 mVPP (with nominal values) Output power: 960 W Maximum no-load power dissipation: 12 W Power loss nominal load max.: 74 W Rise time: < 0.05 s (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK active Output description: UOUT > 0.9 x UN: High signal Switching voltage range: 18 VÃDC ... 24 VÃDC Maximum inrush current: ââ°¤ 20 mA (short-circuit-proof) Continuous load current: ââ°¤ 20 mA Signal: DC OK floating Output description: Relay contact, UOUT > 0.9 x UN: Contact closed Maximum switching voltage: 30 V AC/DC 24 VÃDC Maximum inrush current: 0.5 A 1 A Continuous load current: ââ°¤ 1 A Signal: POWER BOOST, active Output description: IOUT < IN: High signal Switching voltage range: 18 VÃDC ... 24 VÃDC Output voltage: + 48 VÃDC Maximum inrush current: ââ°¤ 20 mA (short-circuit-proof) Continuous load current: ââ°¤ 20 mA
|
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 14 Conductor cross section AWG max.: 10 Stripping length: 7 mm Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.5 mm² Conductor cross section, rigid max.: 16 mm² Conductor cross section flexible min.: 0.5 mm² Conductor cross section flexible max.: 16 mm² Conductor cross section AWG min.: 8 Conductor cross section AWG max.: 6 Stripping length: 10 mm Screw thread: M3 Tightening torque, min: 1.2 Nm Tightening torque max: 1.5 Nm Signal Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 10 Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm
|
Signaling | Types of signaling: LED Active switching output Relay contact Signal output: DC OK active Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED IOUT < IN: LED ON Signal output: DC OK floating Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED Signal output: POWER BOOST, active Status display: IOUT > IN: LED "BOOST" yellow
|
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4 kV AC (type test) 2 kV AC (routine test) Insulation voltage output / PE: 500 VÃDC (routine test) Insulation voltage input / PE: 3.5 kV AC (type test) 2 kV AC (routine test)
|
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 880000 h (25ðC) > 523000 h (40ðC) Insulation characteristics Protection class: I Degree of pollution: 2
|
Dimensions | Width: 180 mm Height: 130 mm Depth: 125 mm Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 50 mm / 50 mm Alternative assembly Width: 122 mm Height: 130 mm Depth: 183 mm
|
Mounting | Assembly instructions: alignable: PN ââ°¥50%, 5Ãmm horizontally, 15Ãmm next to active components, 50Ãmm vertically alignable: PN <50%, 0Ãmm horizontally, 40Ãmm vertically top, 20 mm vertically bottom Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No
|
Material specifications | Housing material: Metal Type of housing: Steel sheet, zinc-plated
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: 6000 m Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ñ2.5 mm (according to IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min.
|
Standards and regulations | Rail applications: ENÃ50121-4 ENÃ50121-3-2 Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: IEC 61010-2-201Ã(SELV) Standard - Equipment safety: BG (design tested) Standard ââ¬Ã¢ Protection against shock currents, basic requirements for protective separation in electrical equipment: ENÃ50178 Standard ââ¬Ã¢ Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Overvoltage category EN 62477-1: III
|
Approvals | CSA: CAN/CSA-C22.2 No.Ã60950-1-07 CSA-C22.2 No.Ã107.1-01 Shipbuilding approval: DNVÃGLÃ(EMCÃA) SIQ: BG (type approved) UL approvals: UL Listed ULÃ508 UL/C-UL Recognized ULÃ60950-1 UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 (EN 55022) Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 3 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 2 kV (Test Level 3 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Emitted interference Standards/regulations: ENÃ61000-6-3 Radio interference voltage in acc. with EN 55011: ENÃ55011 (ENÃ55022) ClassÃB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
|