PHOENIX CONTACT 2866695
PHOENIX CONTACT 2866695
PHOENIX CONTACTNon disponibile

QUINT-PS/1AC/48DC/20 - Power supply unit

Primary-switched power supply unit QUINT POWER, Screw connection, SFB Technology (Selective Fuse Breaking), input:1-phase, output: 48 VDC / 20 A
Cod. Articolo: 2866695
Cod. Fornitore: 2866695
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Input dataAC operation
Nominal input voltage range: 100 VÂAC ... 240 VÂAC
120 VÂDC ... 300 VÂDC (UL 508: ≤ 250 V DC)
Input voltage range: 85 VÂAC ... 264 VÂAC
90 VÂDC ... 300 VÂDC (UL 508: ≤ 250 V DC)
Input voltage range AC: 85 VÂAC ... 264 VÂAC
Input voltage range DC: 90 VÂDC ... 300 VÂDC (UL 508: ≤ 250 V DC)
Electric strength, max.: 300 VÂAC
Voltage type of supply voltage: AC/DC
Inrush current: < 15 A (typical)
Inrush current integral (I2t): < 1.6 A2s
AC frequency range: 45 Hz ... 65 Hz
Frequency range DC: 0 Hz
Mains buffering time: typ. 20 ms (120ÂVÂAC)
typ. 22 ms (230 V AC)
Current consumption: 8.7 A (120ÂVÂAC)
4.5 A (230 V AC)
9.4 A (110ÂVÂDC)
4.6 A (220 VÂDC)
Nominal power consumption: 1046 VA
Protective circuit: Transient surge protection; Varistor
Typical response time: < 0.65 s
Input fuse: 20 A (fast blow, internal)
Permissible backup fuse: B16 B25 AC:
Permissible DC backup fuse: DC: Connect a suitable fuse upstream
Recommended breaker for input protection: 6 A ... 16 A (AC: Characteristics B, C, D, K)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: > 93 % (for 230 V AC and nominal values)
Nominal output voltage: 48 VÂDC ±1Â%
Setting range of the output voltage (USet): 30 VÂDC ... 56 VÂDC (> 48ÂVÂDC, constant capacity restricted)
Nominal output current (IN): 20 A (-25°CÂ...Â60°C, UOUT = 48ÂVÂDC)
POWER BOOST (IBoost): 22.5 A (-25°CÂ...Â40°C permanent, UOUT = 48ÂVÂDC )
Selective Fuse Breaking (ISFB): 100 A (12Âms)
Magnetic circuit breaker tripping: B2 / B4 / B6 / B10 / C2 / C4 / C6
Derating: 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: max. 60 VÂDC
Protection against overvoltage at the output (OVP): < 60 VÂDC
Active current limitation: Approx. IBOOST = 22.5 A (for short-circuit)
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 50 mVPP (with nominal values)
Output power: 960 W
Maximum no-load power dissipation: 12 W
Power loss nominal load max.: 74 W
Rise time: < 0.05 s (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK active
Output description: UOUT > 0.9 x UN: High signal
Switching voltage range: 18 VÂDC ... 24 VÂDC
Maximum inrush current: ≤ 20 mA (short-circuit-proof)
Continuous load current: ≤ 20 mA
Signal: DC OK floating
Output description: Relay contact, UOUT > 0.9 x UN: Contact closed
Maximum switching voltage: 30 V AC/DC
24 VÂDC
Maximum inrush current: 0.5 A
1 A
Continuous load current: ≤ 1 A
Signal: POWER BOOST, active
Output description: IOUT < IN: High signal
Switching voltage range: 18 VÂDC ... 24 VÂDC
Output voltage: + 48 VÂDC
Maximum inrush current: ≤ 20 mA (short-circuit-proof)
Continuous load current: ≤ 20 mA
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Conductor cross section AWG min.: 14
Conductor cross section AWG max.: 10
Stripping length: 7 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.5 mm²
Conductor cross section, rigid max.: 16 mm²
Conductor cross section flexible min.: 0.5 mm²
Conductor cross section flexible max.: 16 mm²
Conductor cross section AWG min.: 8
Conductor cross section AWG max.: 6
Stripping length: 10 mm
Screw thread: M3
Tightening torque, min: 1.2 Nm
Tightening torque max: 1.5 Nm
Signal
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 10
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Active switching output
Relay contact
Signal output: DC OK active
Status display: UOUT > 0.9 x UN: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED
IOUT < IN: LED ON
Signal output: DC OK floating
Status display: UOUT > 0.9 x UN: "DC OK" LED green
Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED
Signal output: POWER BOOST, active
Status display: IOUT > IN: LED "BOOST" yellow
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 500 VÂDC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 880000 h (25°C)
> 523000 h (40°C)
Insulation characteristics
Protection class: I
Degree of pollution: 2
DimensionsWidth: 180 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
Alternative assembly
Width: 122 mm
Height: 130 mm
Depth: 183 mm
MountingAssembly instructions: alignable: PN ≥50%, 5Âmm horizontally, 15Âmm next to active components, 50Âmm vertically
alignable: PN <50%, 0Âmm horizontally, 40Âmm vertically top, 20 mm vertically bottom
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsHousing material: Metal
Type of housing: Steel sheet, zinc-plated
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>Â60°C Derating: 2,5Â%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: 6000 m
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsRail applications: ENÂ50121-4
ENÂ50121-3-2
Standard âۉ€œ Limitation of mains harmonic currents: ENÂ61000-3-2
Standard - Electrical safety: IEC 61010-2-201Â(SELV)
Standard - Equipment safety: BG (design tested)
Standard âۉ€œ Protection against shock currents, basic requirements for protective separation in electrical equipment: ENÂ50178
Standard âۉ€œ Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Overvoltage category
EN 62477-1: III
ApprovalsCSA: CAN/CSA-C22.2 No.Â60950-1-07
CSA-C22.2 No.Â107.1-01
Shipbuilding approval: DNVÂGLÂ(EMCÂA)
SIQ: BG (type approved)
UL approvals: UL Listed ULÂ508
UL/C-UL Recognized ULÂ60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: ENÂ61000-6-3
ENÂ61000-6-4
EMC requirements for noise immunity: ENÂ61000-6-1
ENÂ61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Noise emission: EN 55011 (EN 55022)
Electrostatic discharge
Standards/regulations: ENÂ61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: ENÂ61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: ENÂ61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: ENÂ61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: ENÂ61000-4-6
Conducted interferenceâۉ€¹
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Emitted interference
Standards/regulations: ENÂ61000-6-3
Radio interference voltage in acc. with EN 55011: ENÂ55011 (ENÂ55022) ClassÂB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00054.pdf

Approvals_01229.pdf

Approvals_01302.pdf

Data_sheet_03653.pdf

Manufacturer_declaration_03033.pdf

Manufacturer_declaration_04720.pdf

Manufacturer_declaration_05497.pdf

Manufacturer_declaration_15332.pdf

Package_slip_02070.pdf

Product_information_00152.pdf

Technical_drawing_39063.pdf

Various_00006.pdf

Various_00080.pdf