PHOENIX CONTACT 2902994
PHOENIX CONTACT 2902994
PHOENIX CONTACTNon disponibile

UNO-PS/1AC/24DC/90W/C2LPS - Power supply unit

Primary-switched UNO POWER power supply for DIN rail mounting, input: 1-phase, output: 24 V DC/90 W
Cod. Articolo: 2902994
Cod. Fornitore: 2902994
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Input dataAC operation
Nominal input voltage range: 100 VAC ... 240 VAC
Input voltage range: 85 VAC ... 264 VAC
Input voltage range AC: 85 VAC ... 264 VAC
Voltage type of supply voltage: AC
Inrush current: < 40 A (typ.)
Inrush current integral (I2t): < 1.5 A2s (typ.)
AC frequency range: 50 Hz ... 60 Hz
Frequency range (fN): 50 Hz ... 60 Hz ±10%
Mains buffering time: > 25 ms (120VAC)
> 100 ms (230 V AC)
Current consumption: typ. 1.8 A (100VAC)
typ. 0.8 A (240VAC)
Nominal power consumption: 206.6 VA
Protective circuit: Transient surge protection; Varistor
Power factor (cos phi): 0.49
Typical response time: < 1 s
Input fuse: 3.15 A (slow-blow, internal)
Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K)
Output dataEfficiency: typ. 88 % (120VAC)
typ. 88 % (230 V AC)
Output characteristic: HICCUP
Nominal output voltage: 24 VDC ±1%
Nominal output current (IN): 3.75 A (-25°C...55°C)
Derating: 55°C ... 70°C (2.5%/K)
Feedback voltage resistance: ≤ 35 VDC
Protection against overvoltage at the output (OVP): ≤ 35 VDC
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 45 mVPP (with nominal values)
Short-circuit-proof: yes
Output power: 90 W
Maximum no-load power dissipation: < 0.5 W
Power loss nominal load max.: < 12 W
Rise time: < 0.5 s (UOUT (10 % ... 90 %))
Response time: < 2 ms
Connection in parallel: no
Connection in series: No
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 8 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 8 mm
Screw thread: M3
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
SignalingTypes of signaling: LED
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
3 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: UNO POWER
MTBF (IEC 61709, SN 29500): > 1159000 h (40°C)
Insulation characteristics
Protection class: II (in closed control cabinet)
Degree of pollution: 2
DimensionsWidth: 55 mm
Height: 90 mm
Depth: 84 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 30 mm / 30 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: 0mm horizontally, 30mm vertically
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsFlammability rating according to UL94 (housing / terminal blocks): V0
Housing material: Plastic
Polycarbonate
Type of housing: Polycarbonate
Foot latch material: POM (Polyoxymethylene)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (> 55°C Derating: 2.5 %/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -25°C
Climatic class: 3K22 (in accordance with EN60721-3-3)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 2.3g, 90 min.
Standards and regulationsStandard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard - Electrical safety: IEC 62368-1(SELV)
Standard – Safety extra-low voltage: IEC 62368-1 (SELV) und EN60204-1 (PELV)
Standard - Safe isolation: DINVDE0100-410
Standard - Safety of transformers: EN61558-2-16
Approval - requirement of the semiconductor industry with regard to mains voltage dips: EN61000-4-11
ApprovalsCSA: CAN/CSA-C22.2 No.60950-1-07
CSA-C22.2 No.107.1-01
CAN/CSA-C22.2 No. 213 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UL approvals: UL/C-UL listed UL508
NEC Class 2 as per UL 1310
UL/C-UL Listed ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location)
UL/C-UL Recognized UL60950-1
Conformity/Approvals
SIL in accordance with IEC 61508: 0
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 6 kV (Test Level 3)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion B
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion B
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 1 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Input/Output: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: EN61000-4-11
Voltage: 230 VAC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 25 periods
10 periods
1 period
Additional text: Class3
Comments: Criterion A
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Specifiche
ECLASSECLASS-11.0: 27040701
ECLASS-13.0: 27040701
ECLASS-12.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00048.pdf

Approvals_00049.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Data_sheet_03789.pdf

Manufacturer_declaration_03062.pdf

Manufacturer_declaration_04768.pdf

Manufacturer_declaration_15761.pdf

Manufacturer_declaration_18207.pdf

Package_slip_02525.pdf

Product_information_00033.pdf

Product_information_00057.pdf

Technical_drawing_39684.pdf

Various_00030.pdf

Various_00006.pdf