Input data | AC operation Input voltage range: 100 VÃAC ... 240 VÃAC -15Ã%Ã...Ã+10Ã% Electric strength, max.: 300 VÃAC (60 s) Typical national grid voltage: 120 VÃAC 230 VÃAC Voltage type of supply voltage: AC/DC Inrush current: typ. 9.1 A (at 25ðC) Inrush current integral (I2t): < 0.1 A2s Inrush current limitation: < 9.1 A Frequency range (fN): 50 Hz ... 60 Hz -10Ã%Ã...Ã+10Ã% Mains buffering time: typ. 52 ms (120ÃVÃAC) typ. 52 ms (230 V AC) Current consumption: 0.37 A (100ÃVÃAC) 0.3 A (120ÃVÃAC) 0.17 A (230 V AC) 0.16 A (240ÃVÃAC) Nominal power consumption: 32.8 VA Protective circuit: Transient surge protection; Varistor Typical response time: 350 ms Input fuse: 3.15 A (slow-blow, internal) Recommended breaker for input protection: 6 A ... 16 A (Characteristic B, C or comparable) Discharge current to PE: < 0.25 mA (264ÃVÃAC, 60ÃHz) typ. 0.08 mA DC operation Input voltage range: 110 VÃDC ... 250 VÃDC -20Ã%Ã...Ã+40Ã% Voltage type of supply voltage: AC/DC Current consumption: 0.32 A (110ÃVÃDC) 0.14 A (250ÃVÃDC)
|
Output data | Efficiency: typ. 87.4 % (120ÃVÃAC) typ. 88.4 % (230 V AC) Nominal output voltage: 5 VÃDC Setting range of the output voltage (USet): 5 VÃDC ... 6.2 VÃDC (constant capacity) Nominal output current (IN): 5 A Static Boost (IStat.Boost): 6.25 A (ââ°¤Ã40ðC) Dynamic Boost (IDyn.Boost): 8 A (ââ°¤Ã60ðC (5Ãs)) Feedback voltage resistance: ââ°¤ 16 VÃDC (16ÃV e-caps in output circuit) Protection against overvoltage at the output (OVP): < 8 VÃDC Control deviation: < 0.3 % (change in load, static 10 % ... 90 %) < 3 % (DynamicÃloadÃchangeÃ10%Ã...Ã90%, 10ÃHzÃ<Ã4%) < 0.1 % (change in input voltage ñ10 %) Residual ripple: < 50 mVPP (with nominal values) Short-circuit-proof: yes No-load proof: yes Output power: 25 W 31 W 40 W Maximum no-load power dissipation: < 0.37 W (120ÃVÃAC) < 0.41 W (230 V AC) Power loss nominal load max.: < 3.7 W (120ÃVÃAC) < 3.3 W (230 V AC) Crest factor: typ. 1.88 (120ÃVÃAC) typ. 2.09 (230 V AC) Rise time: 50 ms (UOutÃ=Ã10Ã%Ã...Ã90Ã%) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal (configurable) Digital: 0 VÃDC 10 VÃDC 24 mA Default: 10 VÃDC 24 mA 10ÃVÃDC for UOut >Ã0.9ÃxÃUSet
|
Connection data | Input Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm² Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 10 mm Output Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm² Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 10 mm Signal Connection method: Push-in connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm² Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 Stripping length: 10 mm
|
Signaling | Types of signaling: LED Signal output POut: > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting) UOut: > 0.9ÃxÃUSet (LED lights up green) < 0.9ÃxÃUSet (LED flashes green)
|
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4 kV AC (type test) 3 kV AC (routine test) Switching frequency: 75 kHz ... 220 kHz (Auxiliary converter stage) 4 kHz ... 70 kHz (Main converter stage) 30 kHz ... 135 kHz (PFC stage)
|
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 1890000 h (25ðC) > 1080700 h (40ðC) > 473300 h (60ðC) Insulation characteristics Protection class: II Degree of pollution: 2 Life expectancy (electrolytic capacitors) Current: 2.5 A Temperature: 40°C Time: 91800 h Additional text: 120ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹ Current: 2.5 A Temperature: 40°C Time: 98400 h Additional text: 230ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 2.5 A Temperature: 25°C Time: 183400 h Additional text: 120ÃVÃAC Life expectancy (electrolytic capacitors)ââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Current: 2.5 A Temperature: 25°C Time: 186600 h Additional text: 230ÃVÃAC
|
Dimensions | Width: 22.5 mm Height: 106 mm Depth: 90 mm Installation dimensions Installation distance right/left (active): 15 mm / 15 mm (POutÃââ°¥50%Ã) Installation distance right/left (passive): 5 mm / 5 mm (POutÃââ°¥50%Ã) Installation distance right/left (active, passive): 0 mm / 0 mm (POutÃââ°¤50Ã%) Installation distance top/bottom (active): 30 mm / 30 mm (POutÃââ°¥50%Ã) Installation distance top/bottom (passive): 30 mm / 30 mm (POutÃââ°¥50%Ã) Installation distance top/bottom (active, passive): 30 mm / 30 mm (POutÃââ°¤50Ã%)
|
Mounting | Mounting type: DIN rail mounting With protective coating: No
|
Material specifications | Flammability rating according to ULÃ94 (housing / terminal blocks): V0 Housing material: Plastic Type of housing: Polycarbonate Hood version: Polycarbonate
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5Ã%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ââ°¤ 5000 m (> 2000 m, observe derating) Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): < 15ÃHz, ñ2.5Ãmm amplitude; 15ÃHz ... 100ÃHz: 2.3Ãg 90ÃMin. (in accordance with IEC 60068-2-6)
|
Standards and regulations | Rail applications: ENÃ50121-3-2 ENÃ50121-5 IEC 62236-3-2 IEC 62236-5 Standard ââ¬Ã¢ Limitation of mains harmonic currents: ENÃ61000-3-2 Standard - Electrical safety: IEC 61010-1 (SELV) Standard ââ¬Ã¢ Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61558-2-16 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Standard - Safety of power supply units up to 1100 V (insulation distances): DINÃENÃ61558-2-16 Standard - Safety of transformers: ENÃ61558-2-16 Standard - power supply devices for low voltage with DC output: ENÃ61204-3 Overvoltage category EN 61010-1: IIÃ(ââ°¤Ã5000Ãm) EN 62477-1: IIIÃ(ââ°¤Ã2000Ãm)
|
Approvals | SIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201) UL approvals: UL Listed ULÃ61010-1 UL Listed ULÃ61010-2-201 UL 1310 Class 2 Power Units Conformity/Approvals SIL in accordance with IEC 61508: 0
|
EMC data | EMC requirements for noise emission: ENÃ61000-6-3 ENÃ61000-6-4 EMC requirements for noise immunity: ENÃ61000-6-1 ENÃ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU EMC requirements, power plant: IEC 61850-3 ENÃ61000-6-5 Conducted noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply) ENÃ55016 ENÃ61000-6-3 (Class B) Harmonic currents Standards/regulations: ENÃ61000-3-2 ENÃ61000-3-2 (Class A) Frequency range: 0 kHz ... 2 kHz Flicker Standards/regulations: ENÃ61000-3-3 Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 20 V/m (Test Level X) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 4 kV (Test Level X - asymmetrical) Signal: 4 kV (Test Level X - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: 2 kV (Test Level 4 - symmetrical) 4 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 3 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 0.5 kV (Test Level 2 - symmetrical) 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Power frequency magnetic field Standards/regulations: ENÃ61000-4-8 Frequency: 16.67 Hz 50 Hz 60 Hz 50 Hz 60 Hz 0 Hz Test field strength: 100 A/m 1 kA/m 300 A/m Additional text: 60 s 3 s DC, 60Ãs Comments: Criterion A Frequency range: 50 Hz ... 60 Hz Voltage dips Standards/regulations: ENÃ61000-4-11 Voltage: 100 VÃAC Frequency: 60 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 1Ã/Ã25Ã/Ã30Ãperiods 10Ã/Ã50Ãperiods 0.5 / 1 / 5 / 50 periods Additional text: Test Level 2 Comments: Criterion A Criterion B Pulse-shape magnetic field Standards/regulations: ENÃ61000-4-9 Test field strength: 1000 A/m Comments: Criterion A Attenuated sinusoidal oscillations (ring wave) Standards/regulations: ENÃ61000-4-12 Input: 2 kV (symmetrical) 4 kV (asymmetrical) Comments: Criterion A Asymmetrical conducted disturbance variables Standards/regulations: ENÃ61000-4-16 Test level 1: 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3) Voltage: 30 V (10Ãs) 300 V (1 s) Test level 2: 16.67 Hz 50 Hz 60 Hz (Test Level 2) Comments: Criterion A Attenuated oscillating wave Standards/regulations: ENÃ61000-4-18 Voltage: 1 kV (symmetrical) 2.5 kV (asymmetrical) 1 kV (symmetrical) Comments: Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
|