Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/dadc9c715b207a49982ad6cd5547a214/-S204x204-FJPG Width: 53.6 mm Height: 129.9 mm Depth: 77.14 mm Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715). |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China. |
Material specifications | Color: traffic grey A RAL 7042 |
Interfaces | AxiolineFlocal bus No. of channels: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module Input address area: 2 Byte Output address area: 0 Byte Required parameter data: 6 Byte Required configuration data: 6 Byte |
Input data | Digital Input name: Digital inputs Description of the input: NAMUR enabled digital input signals Number of inputs: 16 (NAMUR) Connection method: Push-in connection Connection technology: 2-conductor Nominal input voltage UIN: 8.2 VDC |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineF connectors |
Electrical properties | Potentials: AxiolineF local bus supply (U Supply voltage: 5 VDC (via bus base module) Current draw: max. 60 mA typ. 40 mA Potentials: Supply for digital input modules (U Supply voltage: 24 VDC Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple) Current draw: max. 130 mA Electrical isolation/isolation of the voltage ranges Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min. Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min. Test voltage: Field to functional earth: 500 VAC, 50 Hz, 1 min. Test voltage: Field to 5V or 24V supplies: 1500 VAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineF connector Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineF: system and installationâ user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C (Standard) -40°C ... 70°C (Extended, see section âTested successfully: use under extreme ambient conditionsâ in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Approvals | ATEX Identification: II 3(1) G Ex ec [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIIC Certificate: DEMKO 20 ATEX 2370X IECEx Identification: Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC Certificate: IECEx UL 20.0044X UKCAEx(UKEX) Identification: II 3(1) G Ex ec [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIIC Certificate: UL22UKEX2508X Ex data UL, USA / Canada: Ind. Cont. Eq. (E238705) also Listed Ind. Cont. Eq. for haz. loc. E196811 Install in: Class I, Div. 2, Groups A, B, C, D T4 Intrinsically safe outputs for: Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz loc Class I, Zone 2, AEx ec [ia Ga] IIC T4 Gc [AEx ia Da] IIIC Ex ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |
Ex data | Safety data Max. output voltage Uo: 10.6 V Max. output current Io: 11 mA Max. output power Po: 30 mW Safety-related maximum voltage Um: 250 V A, B / IIC ((A, B, or IIC)): Max. external inductivity Lo / Max. external capacitance Co: / 2.3 µF 100 mH C/IIB, IIIC ((C, IIB, or IIIC)): Max. external inductivity Lo / Max. external capacitance Co: / 16 µF 100 mH D/IIA, E, F, G, Class III ((D, E, F, G, Class III, or IIA)): Max. external inductivity Lo / Max. external capacitance Co: / 71.8 µF 100 mH |
ECLASS | ECLASS-11.0: 27242604 ECLASS-12.0: 27242604 ECLASS-13.0: 27242604 |
ETIM | ETIM 9.0: EC001599 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products