Industrial Automation
IB IL AI 4/EF-XC-PAC - Analog module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/20a984302842e949b5ce7beb58df3766/-S204x204-FJPG Width: 48.8 mm Height: 135 mm Depth: 71.5 mm Note on dimensions: Housing dimensions |
Interfaces | Inline local bus Number of interfaces: 2 Connection method: Inline data jumper Transmission speed: 500 kbps |
System properties | Module ID code (dec.): 223 ID code (hex): DF Length code (hex): 05 Length code (dec): 05 Process data channel: 80 bit Input address area: 10 Byte Output address area: 10 Byte Register length: 96 bit Required parameter data: 28 Byte Required configuration data: 4 Byte |
Input data | Analog Input name: Analog inputs Description of the input: Differential input, including sensor supply (24 V DC) Number of inputs: 4 A/D conversion time: max. 10 õs A/D converter resolution: 16 bit Connection method: Inline shield connector Connection technology: 2-, 3-, 4-conductor Note regarding the connection technology: shielded Current input signal: 0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA Input resistance current input: typ. 110 é Voltage input signal: 0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V Input resistance of voltage input: typ. 300 ké Data formats: IB IL, IB ST, standardized representation, S7 compatible Limit frequency (3 dB): 500 Hz Measured value resolution: 16 bits (15 bits + sign bit) Protective circuit: Transient protection; Yes, via arresters Overload protection of the current inputs; electronic |
Product properties | Type: modular Product type: I/O component Product family: Inline Scope of delivery: including Inline connectors and marking fields Operating mode: Process data mode with 5 words/1 word PCP Diagnostics messages: Failure of the internal I/O supply I/O error message sent to the bus coupler Failure of or insufficient communications power UL I/O error message sent to the bus coupler I/O error Error message in the process data User error Error message in the process data |
Electrical properties | Potentials Power consumption: typ. 950 mW (entire device) max. 1.25 W (entire device) Potentials: Communications power (U Supply voltage: 7.5 VÃDC (via voltage jumper) Current draw: max. 100 mA typ. 85 mA Potentials: Supply of analog modules (U Supply voltage: 24 VÃDC (via voltage jumper) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 20 mA typ. 13 mA Potentials: Main circuit supply (U Supply voltage: 24 VÃDC (via voltage jumper) Supply voltage range: 19.2 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current draw: max. 200 mA min. 0 mA (No-load) Supply: Designation: Sensor supply UiS Supply voltage: 24 VÃDC (via feed-in from UM) Current consumption: max. 50 mA (per channel) Electrical isolation/isolation of the voltage ranges Test voltage: 7.5 V supply (bus logic), 24 V supply UANA / I/O: 500 VÃAC, 50 Hz, 1 min. Test voltage: 7.5ÃV supply (bus logic), 24ÃV supply UANA / functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: I/O/functional ground: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: Inline connector Conductor connection Connection method: Spring-cage connection Conductor cross section rigid: 0.08 mm² ... 1.5 mm² Conductor cross section flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm Inline connector Connection method: Spring-cage connection Conductor cross section, rigid: 0.08 mm² ... 1.5 mm² Conductor cross section, flexible: 0.08 mm² ... 1.5 mm² Conductor cross section AWG: 28 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 55°C (Standard) -40°C ... 70°C (Extended, see section ââ¬Ã Tested successfully: use under extreme ambient conditionsâ⬠in the data sheet.) Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 10 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting |
Description other products