Industrial Automation
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d8e975a53705df4b84bb84f39d8f66c1/-S204x204-FJPG Width: 53.6 mm Height: 126.1 mm Depth: 77.14 mm Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715). |
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China. |
Material specifications | Color: traffic grey A RAL 7042 |
Interfaces | Axioline P local bus Connection method: Connection for bus base module Transmission speed: 100 Mbps |
Output data | Digital Output name: Digital outputs Connection method: Push-in connection Connection technology: 2-conductor Number of outputs: 4 Protective circuit: Polarity reversal protection of the outputs Output voltage: 21 V Maximum output current per channel: 60 mA Nominal output voltage: 21 V |
Product properties | Type: block modular Product type: I/O component Product family: Axioline P Mounting position: any (no temperature derating) Scope of delivery: including bus base module and connectors Insulation characteristics Overvoltage category: II Pollution degree: 2 |
Electrical properties | Potentials: Supply of the logic voltage U Supply voltage range: 19.2 VDC ... 30 VDC (via bus base module (UL) at AXLPBK...) Potentials: Supply of the AxiolineP local bus U Supply voltage: 5 VDC (via bus base module) Current draw: max. 135 mA Potentials: Axioline P extension module supply voltage Supply voltage: UL (via bus base module) Current draw: max. 455 mA (via bus base module) Electrical isolation/isolation of the voltage ranges Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 62 Hz, 1 min. Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 62 Hz, 1 min. Test voltage: Field to functional earth: 500 VAC, 62 Hz, 1 min. Test voltage: Field to 5V and 24V supplies: 1500 VAC, 62 Hz, 1 min. |
Connection data | Connection technology Connection name: Axioline P connector Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineP: system and installationâ user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm Axioline P connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the âAxiolineP: system and installationâ user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C (Standard) Air pressure (operation): 70 kPa ... 106 kPa (up to 2000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 2000m above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
Approvals | ATEX Identification: II 3(1) G Ex ec [ia IIB Ga] IIC T4 Gc II (1) D [Ex ia Da] IIIC Certificate: DEMKO 20 ATEX 2370X IECEx Identification: Ex ec [ia IIB Ga] IIC T4 Gc [Ex ia Da] IIIC Certificate: IECEx UL 20.0044X UKCAEx(UKEX) Identification: II 3(1) G Ex ec [ia IIB Ga] IIC T4 Gc II (1) D [Ex ia Da] IIIC Certificate: UL22UKEX2508X Ex data UL, USA / Canada: Ind. Cont. Eq. (E238705) also Listed Ind. Cont. Eq. for haz. loc. E196811 Install in: Class I, Div. 2, Groups A, B, C, D T4 Intrinsically safe outputs for: Class I, Groups C, D; Class II, Groups E, F, G; Class III; [Ex ia] Haz loc Class I, Zone 2, AEx ec [ia IIB Ga] IIC T4 Gc [AEx ia Da] IIIC Ex ec [ia IIB Ga] IIC T4 Gc [Ex ia Da] IIIC |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |
Ex data | Safety data Max. output voltage Uo: 24.8 V Max. output current Io: 180 mA Max. output power Po: 1116 mW Safety-related maximum voltage Um: 250 V C/IIB, IIIC: Max. external inductivity Lo / Max. external capacitance Co: / 0.86 µF 2.779 mH D/IIA, E, F, G, Class III: Max. external inductivity Lo / Max. external capacitance Co: / 3.05 µF 7.168 mH |
ECLASS | ECLASS-11.0: 27242604 ECLASS-12.0: 27242604 ECLASS-13.0: 27242604 |
ETIM | ETIM 9.0: EC001599 |
UNSPSC | UNSPSC 21.0: 32151600 |
Description other products