Industrial Automation
Input data | AC operation Supply system configuration: Star network (TN, TT, IT (PE)) Input voltage range: 100 VAC ... 240 VAC -15%...+10% Derating: < 100 VAC ... 85 VAC (1%/V) Typical national grid voltage: 120 VAC 230 VAC Voltage type of supply voltage: AC/DC Inrush current: typ. 37 A Inrush current integral (I2t): typ. 0.4 A2s Frequency range (fN): 50 Hz ... 60 Hz ±10% Mains buffering time: typ. 20 ms (120VAC) typ. 20 ms (230VAC) Current consumption: 1.07 A (100VAC) 0.47 A (240VAC) Protective circuit: Transient surge protection; Varistor Switch-on time: typ. 2 s Device mains fuse: 4 A internal (device protection), slow-blow Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K) Discharge current to PE: < 0.25 mA DC operation Input voltage range: 110 VDC ... 250 VDC -20%...+40% Derating: < 110 VDC ... 88 VDC (1%/V) Current consumption: 0.97 A (110VDC) 0.41 A (250VDC) |
Output data | Efficiency: > 93 % (120VAC) > 94 % (230VAC) Efficiency Level: VI Nominal output voltage: 24 VDC Setting range of the output voltage (USet): 22 VDC ... 27 VDC (> 24 VDC, constant capacity restricted) Nominal output current (IN): 4 A Short-circuit-proof: yes No-load proof: yes Derating: > 50°C ... 70°C (2%/K) Crest factor: typ. 1.74 typ. 2.08 Output power (PN): 96 W Connection in parallel: yes, for increasing power and redundancy with diode Connection in series: yes, for increased output voltage Feedback voltage resistance: ⤠35 VDC Protection against overvoltage at the output (OVP): < 35 VDC Residual ripple: typ. 150 mVPP Control deviation: < 0.5 % (Static load change 10% ... 90%) < 3 % (Dynamic load change 10% ... 90%, (10 Hz)) < 0.1 % (change in input voltage ±10 %) Rise time: typ. 100 ms (UOut=10%...90%) Minimum no-load power dissipation: < 0.21 W (120VAC) Maximum no-load power dissipation: < 0.21 W (230 V AC) Minimum nominal load power dissipation: < 7 W (120VAC) Power loss nominal load max.: < 5.7 W (230 V AC) |
Connection data | Input Position: 1.x Connection technology Position marking: 1.1, 1.2(L), 1.3, 1.4(N) Conductor connection Connection method: Push-in connection rigid: 0.2 mm² ... 2.5 mm² 1 mm² (recommended) flexible: 0.2 mm² ... 2.5 mm² 1 mm² (recommended) flexible with ferrule without plastic sleeve: 0.5 mm² ... 1.5 mm² 1 mm² (recommended) flexible with ferrule with plastic sleeve: 0.2 mm² ... 1 mm² 1 mm² (recommended) rigid (AWG): 24 ... 14 (Cu) 17 (recommended) Stripping length: 10 mm (rigid/flexible) 10 mm (Ferrule) Output Position: 2.x Connection technologyâ Position marking: 2.1, 2.2, 2.3, 2.4 (+), 2.5, 2.6, 2.7, 2.8(-) Conductor connectionâ Connection method: Push-in connection rigid: 0.2 mm² ... 2.5 mm² 1 mm² (recommended) flexible: 0.2 mm² ... 2.5 mm² 1 mm² (recommended) flexible with ferrule without plastic sleeve: 0.5 mm² ... 1.5 mm² 1 mm² (recommended) flexible with ferrule with plastic sleeve: 0.2 mm² ... 1 mm² 1 mm² (recommended) rigid (AWG): 24 ... 14 (Cu) 17 (recommended) Stripping length: 10 mm |
Signaling | LED signaling Types of signaling: LED Signal threshold: > 0,9 x UN (UN = 24VDC) (LED lights up green) < 0,9 x UN (UN = 24VDC) (LED off) |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 4 kV AC (type test) 3.75 kV AC (routine test) |
Product properties | Product type: Power supply Product family: STEPPOWER MTBF (IEC 61709, SN 29500): > 1350000 h (25°C) > 750000 h (40°C) > 488000 h (50°C) Environmental protection directive: RoHS Directive 2011/65/EU WEEE Reach Insulation characteristics Protection class: II (in closed control cabinet) Degree of pollution: 2 |
Dimensions | Item dimensions Width: 72 mm Height: 90 mm Depth: 61 mm 55 mm (Device depth (DIN rail mounting)) Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/705cdbdadb7e4046aaa31deab82c94ff/-S204x204-FJPG Horizontal pitch: 4 Div. (DIN43880) Installation dimensions Installation distance right/left: 0 mm / 0 mm Installation distance top/bottom: 30 mm / 30 mm |
Mounting | Mounting type: DIN rail or direct mounting Assembly instructions: alignable: 0mm horizontally, 30mm vertically Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No |
Material specifications | Flammability rating according to UL 94: V0 (Housing, terminal blocks, base latches) Housing material: Plastic Polycarbonate Foot latch material: Polyamid |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -10°C ... 70°C (Derating: >50°C; 2%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -25°C Maximum altitude: ⤠4000 m (> 2000m, Derating: 10%/1000m) Max. permissible relative humidity (operation): ⤠95 % (at 25°C, non-condensing) Shock (operation): 18ms, 30g, per spatial direction (IEC 60068-2-27) Vibration (operation): < 15 Hz, amplitude ±2.5 mm (IEC 60068-2-6) 15 Hz ... 150 Hz, 2.3g, 90 min. |
Standards and regulations | Overvoltage category EN 61010-1: II(â¤4000m) Overvoltage categoryâ EN 62477-1: III(â¤2000m) Electrical safety Standard designation: Electrical safety Standards/specifications: IEC 61010-1 (SELV) Protective extra-low voltage Standard designation: Protective extra-low voltage Standards/specifications: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Safe isolation Standard designation: Safe isolation Standards/specifications: IEC 61558-2-16 Low-voltage power supplies, DC output Standard designation: Low-voltage power supplies, DC output Standards/specifications: EN61204-3 Safety requirements for electrical equipment for measurement, control, and laboratory use Standard designation: Safety requirements for electrical equipment for measurement, control, and laboratory use Standards/specifications: IEC 61010-1 Household and similar electrical appliances - Safety Standard designation: Safety of electrical devices for household use and similar purposes Standards/specifications: DINEN60335-1 Electric vehicle conductive charging system - Part21-2: EMC requirements for off board electric vehicle charging systems Standard designation: Electric vehicle conductive charging system - Part21-2: EMC requirements for off board electric vehicle charging systems Standards/specifications: IEC 61851-21-2 Note: ClassB |
Approvals | UL Identification: UL/C-UL Listed UL61010-1 ULâ Identification: UL/C-UL Listed UL61010-2-201 ULââ Identification: UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location) |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC Interference emission: Interference emission in accordance with EN61000-6-3 (residential and commercial) and EN61000-6-4 (industrial) Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: EN55016 EN61000-6-3 (Class B) Noise emission: EN55016 EN61000-6-3 (Class B) Harmonic currents Standards/regulations: EN61000-3-2 EN61000-3-2 (Class A) Flicker Standards/regulations: EN61000-3-3 Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: 6 kV (Test Level 3) Discharge in air: 8 kV (Test Level 3) Comments: Criterion A Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: asymmetrical 4 kV (Test Level 4) Output: asymmetrical 2 kV (Test Level 3) Comments: Criterion A Surge voltage load (surge) Standards/regulations: EN61000-4-5 Input: symmetrical 2 kV (Test Level 4) asymmetrical 4 kV (Test Level 4) Output: symmetrical 1 kV (Test Level 3) asymmetrical 2 kV (Test Level 3) Comments: Criterion A Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Input/Output: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: EN61000-4-11 Voltage: 230 VAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 25 periods 10 periods 1 period Additional text: Class3 Comments: Criterion A Criterion B Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
ECLASS | ECLASS-11.0: 27040701 ECLASS-12.0: 27040701 ECLASS-13.0: 27040701 |
ETIM | ETIM 9.0: EC002540 |
UNSPSC | UNSPSC 21.0: 39121000 |
Description other products