Industrial Automation
TRIO3-PS/1AC/24DC/20/8C/IOL - Power supply unit


Input data | AC operation Supply system configuration: Star network (TN, TT, IT (PE)) Nominal input voltage range: 100 VÃAC ... 240 VÃAC Input voltage range: 100 VÃAC ... 240 VÃAC -15Ã%Ã...Ã+10Ã% 115 VÃAC ... 240 VÃAC ñ10Ã% (UL) Derating: < 100 VÃAC (1Ã%/V) 2.5Ã%/K, >Ã60ðC Typical national grid voltage: 120 VÃAC 230 VÃAC Voltage type of supply voltage: AC Inrush current: < 21 A (25ðC) Inrush current integral (I2t): < 1.091 A2s Frequency range (fN): 50 Hz ... 60 Hz ñ10Ã% Mains buffering time: typ. 23 ms (120ÃVÃAC) typ. 24 ms (230 V AC) Current consumption: 5.3 A (100ÃVÃAC) 4.4 A (120ÃVÃAC) 2.3 A (230 VÃAC) 2.15 A (240ÃVÃAC) Protective circuit: Transient protection; Varistor Power factor (cos phi): 0.96 (230 V AC) Device mains fuse: 10 A internal (device protection) Recommended breaker for input protection: 6 A ... 16 A (Characteristic B, C, D, K or comparable) Discharge current to PE: < 3.5 mA DC operation Input voltage range: 100 VÃDC ... 240 VÃDC ñ10Ã% 160 VÃDC ... 240 VÃDC ñ10Ã% (UL) Derating: < 140 VÃDC (1Ã%/V) Voltage type of supply voltage: DC Current consumption: 5.2 A (100ÃVÃDC) 2.1 A (240ÃVÃDC) |
Output data | Efficiency: typ. 93.49 % (120ÃVÃAC) typ. 94.42 % (230 VÃAC) Nominal output voltage: 24 VÃDC Setting range of the output voltage (USet): 24 VÃDC ... 28 VÃDC (> 24 VÃDC, constant capacity restricted) Nominal output current (IN): 20 A Dynamic Boost (IDyn.Boost): max. 30 A (5Ãs) No. of channels: 8 Nominal current per channel: 1 A 2 A 3.8 A 4 A 6 A 8 A 10 A Waiting time after switch off of a channel: 5 s Switch-on delay of the channels: 100 ms Short-circuit-proof: yes No-load proof: yes Derating: 60°C ... 70°C Crest factor: typ. 1.77 (120ÃVÃAC) typ. 1.6 (230 VÃAC) Output power (PN): 480 W Output power (PDyn. Boost): max. 720 W (5Ãs) Connection in parallel: no Connection in series: No Max. capacitive load: 30ÃmF Feedback voltage resistance: ââ°¤ 35 VÃDC Protection against overvoltage at the output (OVP): ââ°¤ 35 VÃDC Residual ripple: typ. 50 mVPP (with nominal values) Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ñ10 %) Rise time: ââ°¤ 1 s (UOutÃ=Ã10Ã%Ã...Ã90Ã%) Minimum no-load power dissipation: < 1.3 W (120ÃVÃAC) Maximum no-load power dissipation: < 1.37 W (230 V AC) Minimum nominal load power dissipation: < 33.37 W (120ÃVÃAC) Power loss nominal load max.: < 26.72 W (230 VÃAC) Integrated fuse protection: yes Signal relay 13/14 Position: 3.x Position marking: 3.1 (13), 3.2 (14) Switch contact (floating): OptoMOS Switching voltage: max. 30 VÃDC (SELV) Current carrying capacity: max. 100 mA State condition: UOut >Ã21ÃVÃDC and IOut <Ã0.9ÃxÃIN (Contact closed) UOut <Ã21ÃVÃDC or IOut >Ã0.9ÃxÃIN Ã(averaging over 60Ãs) (Contact open) Channel triggered or defective or OVP active |
Connection data | Input Position: 1.x Connection technology Position marking: 1.1 (L/+), 1.2 (N/-), 1.3 (ï⬵) Conductor connection Connection method: Push-in connection rigid: 0.2 mm² ... 4 mm² 1.5 mm² (recommended) flexible: 0.2 mm² ... 2.5 mm² 1.5 mm² (recommended) flexible with ferrule without plastic sleeve: 0.25 mm² ... 2.5 mm² 1.5 mm² (recommended) flexible with ferrule with plastic sleeve: 0.25 mm² ... 1.5 mm² 1.5 mm² (recommended) rigid (AWG): 24 ... 12 (Cu) 16 (recommended) Stripping length: 10 mm (rigid/flexible) 8 mm (Ferrule) Output Position: 2.x Connection technologyââ¬Ã¢¹ Position marking: 2.1, 2.2, 2.3, 2.4, 2.5, 2.6, 2.7, 2.8 (+) Conductor connectionââ¬Ã¢¹ Connection method: Push-in connection rigid: 0.2 mm² ... 4 mm² 1.5 mm² (recommended) flexible: 0.2 mm² ... 2.5 mm² 1.5 mm² (recommended) flexible with ferrule without plastic sleeve: 0.25 mm² ... 2.5 mm² 1.5 mm² (recommended) flexible with ferrule with plastic sleeve: 0.25 mm² ... 1.5 mm² 1.5 mm² (recommended) rigid (AWG): 24 ... 12 (Cu) 16 (recommended) Stripping length: 10 mm (rigid/flexible) 8 mm (Ferrule) Outputââ¬Ã¢¹ Position: 2.x Connection technologyââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Position marking: 2.9, 2.10 (-) Conductor connectionââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Connection method: Push-in connection rigid: 0.2 mm² ... 10 mm² 4 mm² (recommended) flexible: 0.2 mm² ... 6 mm² 4 mm² (recommended) flexible with ferrule without plastic sleeve: 0.25 mm² ... 6 mm² 4 mm² (recommended) flexible with ferrule with plastic sleeve: 0.25 mm² ... 6 mm² 4 mm² (recommended) rigid (AWG): 24 ... 8 (Cu) 12 (recommended) Stripping length: 12 mm (rigid/flexible) 12 mm (Ferrule) Signal Position: 3.x Connection technologyââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Position marking: 3.1 (13), 3.2 (14) Conductor connectionââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Connection method: Push-in connection rigid: 0.2 mm² ... 1.5 mm² 0.5 mm² (recommended) flexible: 0.2 mm² ... 1.5 mm² 0.5 mm² (recommended) flexible with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (Cu) 0.5 mm² (recommended) flexible with ferrule with plastic sleeve: 0.25 mm² ... 0.75 mm² 0.5 mm² (recommended) rigid (AWG): 24 ... 16 (Cu) 20 (recommended) Stripping length: 10 mm (rigid/flexible) 8 mm (Ferrule) Communication Position: 5.x Connection technologyââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Position marking: 5.1 (L+), 5.2 (C/Q), 5.3 (L-) Conductor connectionââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Connection method: Push-in connection rigid: 0.2 mm² ... 1.5 mm² 0.5 mm² (recommended) flexible: 0.2 mm² ... 1.5 mm² 0.5 mm² (recommended) flexible with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (Cu) 0.5 mm² (recommended) flexible with ferrule with plastic sleeve: 0.25 mm² ... 0.75 mm² 0.5 mm² (recommended) rigid (AWG): 24 ... 16 (Cu) 20 (recommended) Stripping length: 10 mm (rigid/flexible) 8 mm (Ferrule) |
Interfaces | IO-Link Specification: V1.1 Interface: IO-Link Number of interfaces: 1 Connection method: Push-in connection Position: 5.x Position marking: 5.1 (L+), 5.2 (C/Q), 5.3 (L-) Transmission physics: 3-wire, standard industrial cable Transmission speed: 38.4 kbps (COM2) Cycle time: 40 ms Amount of process data: 6 Byte (Input data) Device ID: 040115hex/262421dez Vendor ID: 00B0hex / 176dez |
Signaling | LED signaling Types of signaling: LED DCÃOK ââ¬Ã¢ signal state operation (UN = 24ÃVÃDC, IOut = IN) Function: Visual operating state display Color: red, yellow, green (multicolor LED) LED off: Supply voltage input AC not present (Off) LED on (green), DC OK: UOut >Ã21ÃVÃDC and IOut <Ã0.9ÃxÃIN (On (green), DC OK) LED on (yellow), IOut > 90%: UOut >Ã21ÃVÃDC and IOut >Ã0.9ÃxÃIN (On (yellow), IOut >Ã90%Ã) LED on (flashing red) OVP: UOUTÃ>ÃOVP (Over voltage protection) (On (flashing red)) |
Electrical properties | Number of phases: 1.00 Insulation voltage input/output: 3 kV AC (type test) 3 kV AC (routine test) |
Product properties | Product type: Power supply Product family: TRIO POWER MTBF (IEC 61709, SN 29500): > 790000 h (25ðC) > 500000 h (40ðC) > 240000 h (60ðC) Environmental protection directive: RoHS Directive 2011/65/EU WEEE Reach Insulation characteristics Protection class: I Degree of pollution: 2 |
Dimensions | Item dimensions Width: 88 mm Height: 135 mm Depth: 132 mm 125 mm (Device depth (DIN rail mounting)) Installation dimensions Installation distance right/left (active): 15 mm / 15 mm Installation distance right/left (passive): 0 mm / 0 mm (ââ°¤Ã40ðC) |
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: 0Ãmm horizontally, 30Ãmm vertically Mounting position: horizontal DIN rail NS 35, EN 60715 |
Material specifications | Flammability rating according to UL 94: V0 (Housing, terminal blocks) Hood version: Polycarbonate Side element version: Aluminum |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Ã60ðC Derating: 2,5 %/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: ââ°¤ 5000 m (> 2000Ãm, Derating: 10Ã%/1000Ãm) Max. permissible relative humidity (operation): ââ°¤ 95 % (at 25°C, non-condensing) Shock (operation): 18Ãms, 30g, per spatial direction (IEC 60068-2-27) Vibration (operation): 10ÃHzÃ...Ã50ÃHz, amplitude ñ0.2Ãmm (IEC 60068-2-6) 50ÃHzÃtoÃ150ÃHz, 2.3Ãg, 90Ãmin. |
Standards and regulations | Overvoltage category EN 61010-1: IIIÃ(ââ°¤Ã2000Ãm) IIÃ(ââ°¤Ã5000Ãm) Overvoltage categoryââ¬Ã¢¹ ENÃ61010-2-201: IIIÃ(ââ°¤Ã2000Ãm) IIÃ(ââ°¤Ã5000Ãm) Safety of power supply units up to 1100ÃV (insulation distances) Standard designation: Safety of power supply units up to 1100ÃV (insulation distances) Standards/specifications: DINÃENÃ61558-2-16 Electrical safety Standard designation: Electrical safety Standards/specifications: IEC 61010-2-201Ã(SELV) Electronic equipment for use in power installations Standard designation: Equipping high voltage installations with electronic equipment Standards/specifications: ENÃ50178/VDEÃ0160Ã(PELV) Safety for measurement, control, and laboratory equipment Standard designation: Safety for equipment for measurement, control, and laboratory use Standards/specifications: IEC 61010-1 Protective extra-low voltage Standard designation: Protective extra-low voltage Standards/specifications: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Safe isolation Standard designation: Safe isolation Standards/specifications: IEC 61558-2-16 IEC 61010-2-201 Limitation of harmonic line currents Standard designation: Limitation of harmonic line currents Standards/specifications: ENÃ61000-3-2 Mains variation/undervoltage Standard designation: Mains variation/undervoltage Standards/specifications: SEMI F47 ENÃ61000-4-11 |
Approvals | UL Identification: UL/C-UL Listed ULÃ61010-1 ULââ¬Ã¢¹ Identification: UL/C-UL Listed ULÃ61010-2-201 ULââ¬Ã¢¹Ã¢Ã¢¬Ã¢¹ Identification: ULÃ2367 (Standard for Safety for Solid State Overcurrent Protectors) ANSI/UL Identification: PROCESS CONTROL EQUIPEMENT FOR HAZARDOUS LOCATIONS (EN) ïâ· This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D, Hazardous Locations, or non-hazardous locations only. (FR) ïâ· Cet appareil convient uniquement pour une utilisation en atmosphères explosibles de classe I, division 2, groupes A, B, C et D ou en atmosphères non explosibles. (EN) ïâ· WARNING: Explosion Hazard - Do not connect or disconnect equipment unless power has been switched off or the area is known to be non-hazardous. (FR) ïâ· AVERTISSEMENTÃ: risque d'explosion - ne pas connecter ou déconnecter les équipements sauf si l'alimentation a été coupée ou si la zone est réputée non dangereuse. (EN) ïâ· If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired. (FR) ïâ· Si l'équipement est utilisé d'une manière non spécifiée par le fabricant, la protection fournie par cet équipement peut être altérée. (EN) ïâ· This equipement must be installed in a suitable, tool secured/key locked enclosure. (FR) ïâ· Cet équipement doit être installé dans un boîtier approprié, verrouillé par une clé ou dont l'ouverture nécessite l'utilisation d'un outil. |
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC Interference emission: Interference emission in accordance with ENÃ61000-6-3 (residential and commercial) and ENÃ61000-6-4 (industrial) Noise immunity: Immunity in accordance with ENÃ61000-6-1 (residential), ENÃ61000-6-2 (industrial) Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Conducted noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Noise emission: ENÃ55016 ENÃ61000-6-3 (Class B) Harmonic currents Standards/regulations: ENÃ61000-3-2 ENÃ61000-3-2 (Class A) Frequency range: 0 kHz ... 2 kHz Flicker Standards/regulations: ENÃ61000-3-3 Frequency range: 0 kHz ... 2 kHz Electrostatic discharge Standards/regulations: ENÃ61000-4-2 Electrostatic dischargeââ¬Ã¢¹ Contact discharge: 6 kV (Test Level 3) Discharge in air: 8 kV (Test Level 3) Comments: Criterion B Electromagnetic HF field Standards/regulations: ENÃ61000-4-3 Electromagnetic HF fieldââ¬Ã¢¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 6 GHz Test field strength: 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÃ61000-4-4 Fast transients (burst)ââ¬Ã¢¹ Input: asymmetrical 2 kV (Test Level 3) Output: asymmetrical 2 kV (Test Level 3) Signal: asymmetrical 1 kV (Test Level 3) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÃ61000-4-5 Input: symmetrical 2 kV (Test Level 4) asymmetrical 4 kV (Test Level 4) Output: symmetrical 1 kV (Test Level 3) asymmetrical 2 kV (Test Level 3) Signal: asymmetrical 1 kV (Test Level 2) Comments: Criterion A Conducted interference Standards/regulations: ENÃ61000-4-6 Conducted interferenceââ¬Ã¢¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Voltage dips Standards/regulations: ENÃ61000-4-11 Voltage: 230 VÃAC Frequency: 50 Hz Voltage dip: 70 % 40 % 0 % Number of periods: 25 periods 10 periods 1 period Additional text: ClassÃ3 Comments: Criterion A Criterion B Criterion A Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements. |
Description other products