Industrial Automation
AXL SE PD16 24V - Potential distributors


Dimensions | Dimensional drawing: https://caas.phoenixcontact.com/caas/v1/stable/media/22530/full/b1500?format=jpg Width: 14.9 mm Height: 62.2 mm Depth: 62 mm |
Notes | Note on application Note on application: Only for industrial use |
Interfaces | Smart Element interface Number of interfaces: 1 Connection method: Card edge connector Transmission speed: See system in which you use the Smart Element. |
System properties | Module ID code (hex): none Process data channel: 0 bit Input address area: 0 Byte (All systems except PROFIBUS) 1 Byte (PROFIBUS) Output address area: 0 Byte Required parameter data: 1 Byte Required configuration data: 6 Byte |
Product properties | Product type: I/O component Product family: Axioline Smart Elements Type: modular Mounting position: See the system in which the Smart Element is used. Special properties: 24 V DC Data management status Article revision: 02 Insulation characteristics Overvoltage category: II (IEC 60664-1, EN 60664-1) Pollution degree: 2 (IEC 60664-1, EN 60664-1) |
Electrical properties | Maximum power dissipation for nominal condition: 1.1 W Potentials: Communications power supply of the Smart Elements (U Supply voltage: using card edge connectors Potentials: I/O supply (U Supply voltage: 24 V DC (using card edge connectors) Supply voltage range: 19.2 V DC ... 30 V DC (including all tolerances, including ripple) Current draw: max. 4 A (2 x 2 A) Current consumption: min. 10 mA (without connected peripherals) Protective circuit: Surge protection; See the system in which the Smart Element is used. Reverse polarity protection; Polarity protection diode Short-circuit/overload protection; electronic fuse (for terminal points 0 ... 7 and 8 ... 15 respectively, 2 A each) Electrical isolation/isolation of the voltage ranges Test voltage: Communications supply / 24 V supply (I/O): 500 V AC, 50 Hz, 1 min. Test voltage: Communications supply / functional ground: 500 V AC, 50 Hz, 1 min. Test voltage: 24 V supply (I/O) / functional ground: 500 V AC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: I/O Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã Axioline Smart Elementsâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.25 mm² ... 1.5 mm² Conductor cross section flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm I/O Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã Axioline Smart Elementsâ⬠user manual. Conductor cross section, rigid: 0.25 mm² ... 1.5 mm² Conductor cross section, flexible: 0.25 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25 °C ... 60 °C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000 m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000 m above sea level) Ambient temperature (storage/transport): -40 °C ... 85 °C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, EN 61140, VDE 0140-1) |
Mounting | Mounting type: Smart Element slot Mounting position: See the system in which the Smart Element is used. |
Description other products