Industrial Automation
Product properties | Product type: Network isolator MTBF: 5446 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 2959 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties | Electrical isolation: Ethernet // Ethernet Insulation voltage input/output: 250 Vrms Test voltage data interface/data interface: 4 kV AC (50Hz, 1min.) |
Connection data | Supply Tightening torque: 0.56 Nm ... 0.79 Nm |
Interfaces | Signal: Ethernet PROFINET Data: Ethernet interface, 10/100/1000Base-T(X) in accordance with IEEE802.3 Serial transmission speed: 10/100/1000 Mbps Connection method: RJ45 jack No. of channels: 1 Transmission length: ⤠100 m (Total length across both ports (dependent on data rate and cable used)) Data: Ethernet interface, 10/100/1000Base-T(X) in accordance with IEEE802.3â Serial transmission speed: 10/100/1000 Mbps Connection method: RJ45 jack No. of channels: 1 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/ca75a5d17da7c3418b16bac0f53351bc/-S204x204-FJPG Width: 22.5 mm Height: 99 mm Depth: 92 mm |
Material specifications | Material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 75°C Ambient temperature (storage/transport): -25°C ... 85°C Altitude: ⤠5000 m (For restrictions, see the manufacturer's declaration for altitude operation) Permissible humidity (operation): 10 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant EAC Identification: EAC UL, USA/Canada Identification: 508 Listed Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A Shipbuilding Identification: DNV GL DNV GL data Temperature: B Humidity: A Vibration: A EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Electrostatic discharge Standards/regulations: EN61000-4-2 Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: 26 MHz ... 3 GHz (Test Level 3) Field intensity: 20 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V Emitted interference Standards/regulations: EN61000-6-4 Radio interference voltage in acc. with EN 55011: ClassB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: ClassB, area of application: Industry and residential |
Standards and regulations | Standards/regulations: EN 50121 and EN 50155 (for railway applications) |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27240692 ECLASS-12.0: 27240692 ECLASS-13.0: 27240692 |
ETIM | ETIM 9.0: EC002584 |
UNSPSC | UNSPSC 21.0: 39121400 |