PHOENIX CONTACT 2316311
PHOENIX CONTACTNot available

FB-8SP ISO - Device coupler

Zone 1 installed device coupler for Foundation Fieldbus and PROFIBUS PA with terminal connections for eight spurs connected to fieldbus end devices.
Product Code: 2316311
Partner cod.: 2316311
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesProduct type: Device coupler
Insulation characteristics
Overvoltage category: II
Degree of pollution: 2
Electrical propertiesSupply
Supply voltage range: 16 VDC ... 32 VDC (input on trunk line side)
Max. current consumption: 35 mA (trunk, no load)
350 mA (maximum trunk current)
Connection dataSupply
Conductor cross section, flexible: 2.50 mm² ... 0.20 mm²
Conductor cross section, rigid: 2.50 mm² ... 0.20 mm²
Conductor cross section, flexible [AWG]: 24 ... 12
Conductor cross section AWG: 24 ... 12
Ex dataSafety data
Input voltage Ui: 32 V
Inductance Li: 0 µH
Capacitance Ci: 0 µF
Max. output voltage Uo: 16.7 V
Max. output current Io: 250 mA
Max. output power Po: 1.05 W
Safety-related maximum voltage Um: 253 V
IIC: Max. external inductivity Lo / Max. external capacitance Co: / 0.39 µF
0.56 mH
IIB: Max. external inductivity Lo / Max. external capacitance Co: / 2.33 µF
2.27 mH
InterfacesSignal: FOUNDATION Fieldbus
PROFIBUS
Data: Foundation Fieldbus and PROFIBUS PA Segment
Connection method: Pluggable COMBICON screw connection for each spur
No. of channels: 8
Termination resistor: Integrated termination, activated with bridge located in correct terminals
Conductor cross section flexible max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section AWG max.: 12
Conductor cross section AWG min.: 24
Output nominal voltage: ≤ 14 V (each spur)
Output current: 35 mA (per spur)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f54716aa18486942b3fc7f2a3380a22d/-S204x204-FJPG
Width: 279 mm
Height: 142 mm
Depth: 66 mm
Material specificationsFlammability rating according to UL 94: V0
Cable/lineCable impedance: Recommend Type A fieldbus cable
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
IP30 (over trunk connections)
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 85°C
Max. permissible relative humidity (operation): < 95 % (non-condensing)
Permissible humidity (operation): 95 % (non-condensing)
Shock: 15g for 11 ms
Vibration (operation): 2g, 10 Hz ... 150 Hz
ApprovalsATEX
Identification: II 2(1) G Ex eb ib mb [ia Ga] IIC T4 Gb
II (1D) [Ex ia Da] IIIC
FISCO power supply (spur)
Certificate: DEMKO 16ATEX 1689X
IECEx
Identification: Ex eb ib mb [ia Ga] IIC T4 Gb
[Ex ia Da] IIIC
FISCO power supply (spur)
Certificate: IECEx UL 16.0114X
UKCAEx(UKEX)
Identification: II 2(1) G Ex eb ib mb [ia Ga] IIC T4 Gb
II (1D) [Ex ia Da] IIIC
FISCO power supply (spur)
Certificate: UL21UKEX2210X
CCCEx
Identification: Ex eb ib mb [ia Ga] IIC T4 Gb
[Ex ia Da] IIIC
Ex data
UL, USA / Canada: Install in Class I, Div. 2, Groups A, B, C, D
Entity/FISCO spur to: Class I, Groups A, B, C, D; Class II, Groups E, F, G; Class III; Group IIIC
Class I, Zone 1 AEx eb ib mb [ia Ga] IIC T4 Gb
[AEx ia Da] IIIC
FISCO power supply (spur)
Ex eb ib mb [ia Ga] IIC T4 Gb
[Ex ia Da] IIIC
FISCO power supply (spur)
Standards and regulationsStandards/regulations
Standards/regulations: Ring wave noise immunity in acc. with IEC 61000-4-12
Standards/regulations​
Standards/regulations: Dry heat in acc. with IEC 61131-2
Standards/regulations​​
Standards/regulations: Damp heat in acc. with IEC 61131-2
Standards/regulations​​​
Standards/regulations: Shock and vibration in acc. with EN 61131-2 and EN 50178
IEC 61158-2
MountingMounting type: DIN rail mounting
Mounting position: On horizontal and vertical DIN rail NS 35 in acc. with EN 60715
Technical Specs
ECLASSECLASS-11.0: 27242610
ECLASS-12.0: 27242610
ECLASS-13.0: 27242610
ETIMETIM 9.0: EC001600
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00498.pdf

Approvals_00499.pdf

Approvals_00879.pdf

Data_sheet_03087.pdf

Manufacturer_declaration_00124.pdf

Manufacturer_declaration_02924.pdf

Manufacturer_declaration_05549.pdf

Manufacturer_declaration_14255.pdf

Package_slip_00087.pdf

Product_information_00033.pdf

Product_information_00198.pdf

Technical_drawing_37347.pdf