Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2688022
PHOENIX CONTACTNot available

AXL F DI16/4 2F - Digital module

AxiolineF, Digital input module, Digital inputs: 16, 24 VDC, connection technology: 4-conductor, transmission speed in the local bus:100 Mbps, degree of protection: IP20, including bus base module and AxiolineF connectors
Product Code: 2688022
Partner cod.: 2688022
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Download
Tecnichal data
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f4dbc4c57447e643bed727029bb8cde0/-S204x204-FJPG
Width: 53.6 mm
Height: 129.9 mm
Depth: 54 mm
Note on dimensions: The depth applies when a TH35-7.5 DIN rail is used (in accordance with EN60715).
InterfacesAxiolineFlocal bus
Number of interfaces: 2
Connection method: Bus base module
Transmission speed: 100 Mbps
System propertiesModule
ID code (hex): none
Input address area: 2 Byte
Output address area: 0 Byte
Required parameter data: 3 Byte
Required configuration data: 6 Byte
Input dataDigital
Input name: Digital inputs
Description of the input: EN 61131-2 types 1 and 3
Number of inputs: 16
Connection method: Push-in connection
Connection technology: 4-conductor
Input voltage range "0" signal: -3 VDC ... 5 VDC
Input voltage range "1" signal: 11 VDC ... 30 VDC
Nominal input voltage UIN: 24 VDC
Nominal input current at UIN: 2.4 mA
Input filter time: 500 µs (Default)
< 100 µs
Protective circuit: Polarity reversal protection of the inputs; electronic
Product propertiesType: block modular
Product type: I/O component
Product family: AxiolineF
Mounting position: any (no temperature derating)
Scope of delivery: including bus base module and AxiolineF connectors
Insulation characteristics
Overvoltage category: II (IEC 60664-1, EN60664-1)
Pollution degree: 2 (IEC 60664-1, EN60664-1)
Electrical propertiesMaximum power dissipation for nominal condition: 96 W
Potentials: AxiolineF local bus supply (U
Supply voltage: 5 VDC (via bus base module)
Current draw: max. 120 mA (up to HW 04)
max. 60 mA (from HW 05)
Power consumption: max. 600 mW (up to HW 04)
max. 300 mW (from HW 05)
Potentials: Supply for digital input modules (U
Supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (including all tolerances, including ripple)
Current draw: max. 4 A (Sensor supply US)
Power consumption: max. 120 W (of which 800mW with internal losses)
Protective circuit: Surge protection; electronic (35 V, 0.5 s)
Reverse polarity protection; parallel diode; with external 5A fuse (only for commissioning)
Supply: Sensor supply (US)
Designation: Sensor supply (US)
Supply voltage: 24 VDC (from UI)
Electrical isolation/isolation of the voltage ranges
Test voltage: 5V supply of the local bus (UBus) / 24V supply (I/Os): 500 VAC, 50 Hz, 1 min.
Test voltage: 5V supply of the local bus (UBus) / functional ground: 500 VAC, 50 Hz, 1 min.
Test voltage: 24V supply (I/O) / functional ground: 500 VAC, 50 Hz, 1 min.
Connection dataConnection technology
Connection name: AxiolineF connector
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor connection
Connection method: Push-in connection
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
AxiolineF connector
Connection method: Push-in connection
Note on the connection method: Please observe the information provided on conductor cross sections in the “AxiolineF: system and installation” user manual.
Conductor cross section, rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section, flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Stripping length: 8 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP20
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level)
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing)
Standards and regulationsProtection class: III (IEC 61140, EN61140, VDE0140-1)
MountingMounting type: DIN rail mounting
Mounting position: any (no temperature derating)
Technical Specs
ECLASSECLASS-11.0: 27242604
ECLASS-12.0: 27242604
ECLASS-13.0: 27242604
ETIMETIM 9.0: EC001599
UNSPSCUNSPSC 21.0: 32151600
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00785.pdf

Approvals_01195.pdf

Approvals_01203.pdf

Approvals_01209.pdf

Approvals_01303.pdf

Approvals_01758.pdf

Approvals_01816.pdf

Approvals_01836.pdf

Approvals_01893.pdf

Approvals_01935.pdf

Data_sheet_03149.pdf

Manual_00007.pdf

Manual_00006.pdf

Manufacturer_declaration_00591.pdf

Manufacturer_declaration_02225.pdf

Manufacturer_declaration_05480.pdf

Manufacturer_declaration_05562.pdf

Manufacturer_declaration_05563.pdf

Manufacturer_declaration_14397.pdf

Package_slip_00638.pdf

Package_slip_00716.pdf

Product_information_00033.pdf

Product_information_00229.pdf

Product_information_00230.pdf

Technical_drawing_37495.pdf

Various_00004.pdf