Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2700282
PHOENIX CONTACT 2700282
PHOENIX CONTACTNot available

AXL E IOL AO1 I M12 R - Analog module

AxiolineE-IO-Link/analog converter for connecting an analog actuator, 4mA ... 20mA, M12 fast connection technology, angled version
Product Code: 2700282
Partner cod.: 2700282
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesType: Stand-Alone
AxiolineÂE
Angled
Product type: Interface converter
Product family: AxiolineÂE
Diagnostics messages: Short circuit Message in the diagnostic code (in the IBÂIL format)
Configuration invalid Message in the diagnostic code (in the IBÂIL format)
Module faulty Message in the diagnostic code (in the IBÂIL format)
Insulation characteristics
Pollution degree: 2
Electrical propertiesSupply: IO-Link
Nominal voltage for I/O supply: 24 VÂDC (This supply voltage is provided via the IO-Link interface of the IO-Link master.)
Nominal current for every IO-Link port: max. 100 mA
Current consumption: typ. 16.5 mA ±15Â% (at 24 V DC)
max. 135 mA
Protective circuit: Reverse polarity protection
Short-circuit protection
Overload protection
Input dataIO-Link
Number of ports: 1
Connection method: M12 connector, A-coded
Connection technology: 3-conductor
Specification: V1.1.1
Reverse polarity protection: yes
Cycle Time: min. 2 ms
Process data update: 2 ms
Amount of process data: 16 bit (Input data)
16 bit (Output data)
Output dataAnalog
Output name: Analog output
Connection method: M12 connector, A-coded
Connection technology: 3-conductor
Number of outputs: 1 (current)
D/A converter resolution: 12 bit
Data formats: IB IL, S7-compatible
Current output signal: 4 mA ... 20 mA
Load/output load current output: max. 500 Ω
Permissible cable length: max. 30 m (Shielded cable)
SignalingDiagnostic messages
Diagnostics: Short circuit
Message: Message in the diagnostic code (in the IBÂIL format)
Diagnostic messagesâۉ€¹
Diagnostics: Configuration invalid
Message: Message in the diagnostic code (in the IBÂIL format)
Diagnostic messagesâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Diagnostics: Module faulty
Message: Message in the diagnostic code (in the IBÂIL format)
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/65fd57f6da67f24496626511618a6a99/-S204x204-FJPG
Width: 16.6 mm
Height: 42 mm
Depth: 66.5 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -25°C ... 60°C
Degree of protection: IP65/IP67
Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Âm above sea level)
Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Âm above sea level)
Ambient temperature (storage/transport): -25°C ... 85°C
Permissible humidity (operation): 5 % ... 95 %
Permissible humidity (storage/transport): 5 % ... 95 %
Standards and regulationsProtection class: III (IEC 61140, ENÂ61140, VDEÂ0140-1)
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01216.pdf

Approvals_01217.pdf

Data_sheet_03206.pdf

Manual_00152.pdf

Manufacturer_declaration_00744.pdf

Manufacturer_declaration_02150.pdf

Manufacturer_declaration_05478.pdf

Manufacturer_declaration_14454.pdf

Package_slip_00653.pdf

Technical_drawing_37606.pdf

Various_00004.pdf