Industrial Automation
AXL E IOL RTD1 M12 S - Analog module
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Type: Stand-Alone AxiolineE straight Product type: Interface converter Product family: AxiolineE Diagnostics messages: Overrange or underrange Message in the diagnostic code (in the IBIL format) Measured value invalid/no valid measured value present Message in the diagnostic code (in the IBIL format) Configuration invalid Message in the diagnostic code (in the IBIL format) Module faulty Message in the diagnostic code (in the IBIL format) Insulation characteristics Pollution degree: 2 |
Electrical properties | Supply: IO-Link Nominal voltage for I/O supply: 24 VDC (This supply voltage is provided via the IO-Link interface of the IO-Link master.) Current consumption: typ. 16.5 mA ±15% (at 24 V DC) max. 25 mA Protective circuit: Reverse polarity protection Short-circuit protection Overload protection |
Input data | IO-Link Number of ports: 1 Connection method: M12 connector, A-coded Connection technology: 3-conductor Specification: V1.1.1 Reverse polarity protection: yes Cycle Time: min. 2 ms Process data update: 2 ms Amount of process data: 16 bit (Input data) 16 bit (Output data) Analog Input name: Analog RTD input Description of the input: Input for resistive temperature sensors Number of inputs: 1 (for resistance temperature detectors) Connection method: M12 connector, A-coded Connection technology: 3-conductor (4-conductor as an option) A/D converter resolution: 12 bit Sensor types (RTD) that can be used: Pt100, Pt1000 Data formats: IB IL, S7-compatible Linear resistance measuring range: 0 é ... 500 é (IB IL format) 0 é ... 5 ké (IB IL format) 0 é ... 600 é (Format S7 compatible) 0 é ... 6 ké (Format S7 compatible) Protective circuit: Reverse polarity protection Short-circuit protection Overload protection |
Signaling | Diagnostic messages Diagnostics: Overrange or underrange Message: Message in the diagnostic code (in the IBIL format) Diagnostic messagesâ Diagnostics: Measured value invalid/no valid measured value present Message: Message in the diagnostic code (in the IBIL format) Diagnostic messagesââ Diagnostics: Configuration invalid Message: Message in the diagnostic code (in the IBIL format) Diagnostic messagesâââ Diagnostics: Module faulty Message: Message in the diagnostic code (in the IBIL format) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/5ff5351b4a5945449f260aadda9c6dca/-S204x204-FJPG Width: 16.6 mm Height: 29 mm Depth: 79.5 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP65/IP67 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000m above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000m above sea level) Ambient temperature (storage/transport): -25°C ... 85°C Permissible humidity (operation): 5 % ... 95 % Permissible humidity (storage/transport): 5 % ... 95 % |
Standards and regulations | Protection class: III (IEC 61140, EN61140, VDE0140-1) |
ECLASS | ECLASS-11.0: 27242601 ECLASS-12.0: 27242601 ECLASS-13.0: 27242601 |