Industrial Automation
Product properties | Product type: Safety relays Product family: PSRmini Application: Emergency stop Safety door Light grid Solenoid switch Transponder Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3 Times Typical response time: < 220 ms (automatic start) < 175 ms (manual, monitored start) Typ. starting time with Us: < 250 ms (when controlled via A1) Typical release time: < 20 ms (on demand via the sensor circuit) < 20 ms (on demand via A1) Restart time: < 1 s (Boot time) Recovery time: < 500 ms |
Electrical properties | Maximum power dissipation for nominal condition: 6.45 W (US=30V, UL=30V, I²=72A²) Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 320 V Rated surge voltage/insulation: Basic insulation 4 kV between all current paths and housing Safe isolation, reinforced insulation 4kV between input circuit and enabling current path (13/14) and enabling current path (23/24) Supply Designation: L+/L- Nominal voltage for I/O supply: 24 VDC -20%/+25% (Provided via the IO-Link interface of the IO-Link master.) Current consumption: typ. 16 mA Protective circuit: Serial protection against polarity reversal; Suppressor diode Supplyâ Designation: A1/A2 Rated control circuit supply voltage US: 19.2 VDC ... 30 VDC 24 VDC -20%/+25% (provide external protection) Rated control supply current IS: typ. 60 mA Power consumption at US: typ. 1.44 W Inrush current: typ. 2.5 A (Ãt=500µs at Us) Filter time: 1 ms (at A1 in the event of voltage dips at Us) Protective circuit: Serial protection against polarity reversal; Suppressor diode |
Input data | Digital: Sensor circuit S0 (S12, S22) Description of the input: safety-related sensor inputs Number of inputs: 2 Input voltage range "0" signal: 0 VDC ... 5 VDC (S12) For S22, see note in âSignal generator connection versionsâ section. Input voltage range "1" signal: 11 VDC ... 30 VDC Input current range "0" signal: 0 mA ... 2 mA (S12, S22) Inrush current: < 5 mA (typ. with US at S12, Ãt=150ms) < 5 mA (typically with US at S22/24V, Ãt=500µs) > -5 mA (typically with US at S22/0V, Ãt=500µs) Filter time: 1.5 ms (Test pulse width of low test pulses) Test pulse rate=5xTest pulse width Deactivate the switch-on pulses for safety applications. Concurrence: â Max. permissible overall conductor resistance: 150 é Protective circuit: Suppressor diode Current consumption: < 5 mA (Typically with US at S12) < 5 mA (typically with US at S22/24V) > -5 mA (typically with US at S22/0V) Digital: Sensor circuit S1 (S32, S42) Description of the input: safety-related sensor inputs Number of inputs: 2 Input voltage range "0" signal: 0 VDC ... 5 VDC Input voltage range "1" signal: 11 VDC ... 30 VDC Input current range "0" signal: 0 mA ... 2 mA Inrush current: < 20 mA (typically with US) Filter time: max. 1.5 ms (Test pulse width of low test pulses) Test pulse rate=5xTest pulse width Deactivate the switch-on pulses for safety applications. Concurrence: â Max. permissible overall conductor resistance: 150 é Protective circuit: Suppressor diode Current consumption: < 5 mA (typically with US) Digital: Diagnostic input (DGN) Description of the input: non-safety-related Number of inputs: 1 Input voltage range: 0 VDC ... 30 VDC Protective circuit: Suppressor diode Current consumption: typ. 30 mA Digital: Start circuit (S34) Number of inputs: 1 Input voltage range "1" signal: 19.2 VDC ... 30 VDC (manual start, autostart: 0V) Inrush current: < 10 mA (typically with US, Ãt=100ms) Max. permissible overall conductor resistance: 150 é Protective circuit: Suppressor diode Current consumption: < 5 mA (typically with US at S34/24V) > -5 mA (typically with US at S34/0V) IO-Link Designation: IO-Link Transmission speed: 230 kbps (COM3) Cycle Time: 5 ms Process data update: 5 ms Amount of process data: max. 31 Byte (Input data) max. 16 Byte (Output data) Description of the input: IO-Link switching and communication cable Number of inputs: 1 Connection method: Screw connection Connection technology: 3-conductor Number of ports: 1 Port type: Class A |
Output data | Relay: Enabling current path (13/14, 23/24) Output description: safety-related N/O contacts 2 NO contacts each in series, without delay, floating Number of outputs: 2 (undelayed) Contact switching type: 2 enabling current paths Contact material: AgSnO2 Switching voltage: min. 12 V AC/DC max. 250 V AC/DC (Observe the load curve) Switching capacity: min. 60 mW Inrush current: min. 3 mA max. 6 A Switching capacity in accordance with IEC 60947-5-1: 4 A (24V (DC13)) 5 A (250V (AC15)) Limiting continuous current: 6 A Sq. Total current: 72 A2 (observe derating) Switching frequency: 0.5 Hz Mechanical service life: 10x 106 cycles Output fuse: 6 A gL/gG 4 A gL/gG (for low-demand applications) Signal: M1 Output description: PNP non-safety-related Number of outputs: 1 Voltage: approx. 22 VDC (Us-2V) Current: max. 100 mA Maximum inrush current: 500 mA (Ãt=1ms at Us) Protective circuit: Suppressor diode |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Screw connection Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross-section AWG: 24 ... 12 Stripping length: 7 mm Screw thread: M3 Tightening torque: 0.5 Nm ... 0.6 Nm |
Signaling | Status display: 5x LED green Operating voltage display: 1 x green, yellow, red LED |
Dimensions | Width: 17.5 mm Height: 112.2 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 Safety data: ENISO13849 Category: 4 Performance level (PL): e (4ADC13; 5AAC15; 8760switching cycles/year) Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 3 Safety data: IEC 61508 - Low demand Safety Integrity Level (SIL): 3 Safety data: ENIEC 62061 Safety Integrity Level (SIL): 3 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -25°C ... 60°C (observe derating) Ambient temperature (storage/transport): -40°C ... 85°C Maximum altitude: ⤠2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g Vibration (operation): 10Hz...150Hz, 2g |
Approvals | CE Identification: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: DINEN60947-1 |
Mounting | Mounting type: DIN rail mounting Assembly instructions: See derating curve Mounting position: vertical or horizontal Connection method: Screw connection |
ECLASS | ECLASS-11.0: 27371819 ECLASS-13.0: 27371819 ECLASS-12.0: 27371819 |
ETIM | ETIM 9.0: EC001449 |
UNSPSC | UNSPSC 21.0: 39122200 |
Description other products