Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Media converter MTTF: 789 Years (SN29500 standard, temperature25°C, operating cycle21%) 324 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 134 Years (SN29500 standard, temperature40°C, operating cycle100%) MTBF: 177 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 26 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties | Electrical isolation: VCC // V.24 (RS-232) Maximum power dissipation for nominal condition: 2.88 W Test voltage data interface/power supply: 1.5 kVrms (50Hz, 1min.) Supply Supply voltage range: 18 VDC ... 30 VDC Nominal supply voltage: 24 VDC (in acc. with UL) Typical current consumption: 120 mA (24VDC) Max. current consumption: 120 mA |
Output data | Switching Output name: Relay output Output description: Alarm output Number of outputs: 1 Maximum switching voltage: 60 VDC 42 VAC Limiting continuous current: 0.46 A |
Connection data | Supply Connection method: COMBICON plug-in screw terminal block Tightening torque: 0.56 Nm ... 0.79 Nm |
Interfaces | Bit distortion, input: ± 35 % (permitted) Bit distortion, output: < 6.25 % Signal: Modbus Transmission channels: 2 (1/1), RxD, TxD, full duplex Data: optical FO No. of channels: 2 Transmit capacity, minimum: -4.6 dBm (200/230µm) -17.6 dBm (50/125µm) -13.6 dBm (62,5/125 µm) Transmission length incl. 3 dB system reserve: 2800 m (F-K 200/230 8dB/km with quick mounting connector) 4200 m (with F-G 50/125 2.5 dB/km) 4800 m (with F-G 62,5/125 3.0 dB/km) Transmission protocol: Transparent to protocol for RS-232 interface Connection method: B-FOC (ST®) Wavelength: 850 nm Minimum receiver sensitivity: -33.2 dBm Transmission medium: PCF fiber Multi-mode fiberglass Data: V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN66259-1 Serial transmission speed: 4.8Kbps...115.2Kbps Connection method: D-SUB9 plug Transmission length: ⤠15 m Single conductor/terminal point, rigid: 0.2 mm² ... 2.5 mm² Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 14 Min. AWG conductor cross section, flexible: 24 Single-wire/terminal point, rigid AWG max.: 14 Single-wire/terminal point, rigid AWG min.: 24 Transmission medium: Copper File format/coding: UART (11 Bit, NRZ) Data direction switching: Automatic control |
Dimensions | Width: 35 mm Height: 99 mm Depth: 105 mm |
Material specifications | Material: PA 6.6-FR |
Cable/line | FO cable Fiber types: 200/230µm 50/125 µm 62.5/125 µm PCF fiber Fiberglass |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -20°C ... 60°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠5000 m (For restrictions, see the manufacturer's declaration for altitude operation) Permissible humidity (operation): 30 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant EAC Identification: EAC ATEX Identification: ï II 3 G Ex nA nC IIC T4 Gc X Note: Please follow the special installation instructions in the documentation! ATEX, FO interface Identification: ï II (2) G [Ex op is Gb] IIC ï II (2) D [Ex op is Db] IIIC Certificate: PTB06ATEX2042U Note: Please follow the special installation instructions in the documentation! UL, USA/Canada Identification: Class I, Zone 2, AEx nc IIC T5 Class I, Zone 2, Ex nC nL IIC T5 X Class I, Div. 2, Groups A, B, C, D Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A |
EMC data | Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 55011 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: ± 6 kV Discharge in air: ± 8 kV Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Comments: Criterion B Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Comments: Criterion A Voltage: 10 V Emitted interference Standards/regulations: EN55011 Comments: Class A, industrial applications Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
Standards and regulations | Free from substances that could impair the application of coating: in accordance with VW-AUDI-Seat central standard P-VW 3.10.7 57 65 0 |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 19170411 ECLASS-12.0: 19170411 ECLASS-13.0: 19170411 |
ETIM | ETIM 9.0: EC001467 |
UNSPSC | UNSPSC 21.0: 43201500 |
Description other products