Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area Utilization restrictionâ CCCex note: Use in potentially explosive areas is not permitted in China. |
Product properties | Product type: Interface converter Application: RS-232 MTBF: 2263 Years (Telcordia standard, 25°C temperature, 21% operating cycle (5 days a week, 8 hours a day)) 438 Years (Telcordia standard, 40°C temperature, 34.25% operating cycle (5 days a week, 12 hours a day)) |
Electrical properties | Electrical isolation: VCC // V.24 (RS-232) (A) // V.24 (RS-232) (B) Maximum power dissipation for nominal condition: 0.96 W Test voltage data interface/power supply: 2 kVrms (50Hz, 1min.) 2 kV AC Test voltage data interfaces: 2 kV AC Supply Supply voltage range: 19.2 V AC/DC ... 28.8 V AC/DC Nominal supply voltage: 24 V AC/DC ±20% Typical current consumption: 40 mA (24VDC) Protective circuit: Surge protection; Suppressor diode |
Connection data | Supply Tightening torque: 0.56 Nm ... 0.79 Nm |
Interfaces | Bit distortion: < 5 % Bit delay: < 3 µs Signal: Modbus Transmission channels: 4 (2/2), RxD, TxD, RTS, CTS; full duplex Data: V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN66259-1 Serial transmission speed: 115.2 kbps Connection method: D-SUB9 plug Pin assignment: DTE/DCE switchover via switch Transmission length: 15 m (shielded twisted pair) Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 13 Min. AWG conductor cross section, flexible: 24 Protocols supported: transparent protocol Data: V.24 (RS-232) interface in acc. with ITU-T V.28, EIA/TIA-232, DIN66259-1â Connection method: Pluggable screw connection Transmission length: 15 m (shielded twisted pair) Single-wire/terminal point, flexible: 0.2 mm² ... 2.5 mm² Max. AWG conductor cross section, flexible: 13 Min. AWG conductor cross section, flexible: 24 |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/d5d8fb589b189545a32006c46a180100/-S204x204-FJPG Width: 22.5 mm Height: 99 mm Depth: 118.6 mm |
Material specifications | Material: PA |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): 0°C ... 55°C Ambient temperature (storage/transport): -40°C ... 85°C Altitude: ⤠5000 m (For restrictions, see the manufacturer's declaration for altitude operation) Permissible humidity (operation): 10 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant EAC Identification: EAC UL, USA/Canada Identification: 508 Recognized Class I, Div. 2, Groups A, B, C, D Class I, Zone 2, AEx nA IIC T4 Class I, Zone 2, Ex nA IIC T4 Gc X Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A Shipbuilding Identification: DNV GL DNV GL data Temperature: B Humidity: A Vibration: A EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2:2005 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 61000-6-3 Electrostatic discharge Standards/regulations: EN61000-4-2 Electrostatic dischargeâ Contact discharge: ± 6 kV (Test Level 3) Discharge in air: ± 8 kV (Test Level 3) Comments: Criterion B Electromagnetic HF field Standards/regulations: EN61000-4-3 Electromagnetic HF fieldâ Frequency range: Test Level 3 Field intensity: 10 V/m Comments: Criterion A Fast transients (burst) Standards/regulations: EN61000-4-4 Fast transients (burst)â Input: ± 4 kV (5kHz) Signal: ± 2 kV (5kHz) Comments: Criterion B Surge current load (surge) Standards/regulations: EN61000-4-5 Surge current load (surge)â Input: ± 0.5 kV (2 é) Signal: ± 2 kV (12é) Comments: Criterion B Conducted interference Standards/regulations: EN61000-4-6 Conducted interferenceâ Comments: Criterion A Voltage: 10 V Emitted interference Standards/regulations: EN55011 Comments: Class A, industrial applications Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself. |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27242208 ECLASS-12.0: 27242208 ECLASS-13.0: 27242208 |
ETIM | ETIM 9.0: EC001423 |
UNSPSC | UNSPSC 21.0: 32151700 |