PHOENIX CONTACT 2811860
PHOENIX CONTACT 2811860
PHOENIX CONTACTNot available

MACX MCR-T-UI-UP-SP - Temperature measuring transducer

Freely programmable temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer in 2-, 3-, or 4-conductor technology, thermocouples, electrical isolation, wide-range power supply, Push-in connection, SIL, PL.
Product Code: 2811860
Partner cod.: 2811860
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesProduct type: Temperature transmitter
Product family: MACX Analog
Type: Signal conditioners with SIL and PL Functional Safety
Configuration: DIP switches
Software
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
Electrical propertiesElectrical isolation: 4-way isolation
Maximum power dissipation for nominal condition: 1.26 W
Step response (0–99%): ≤ 1.75 s (SILon)
1.3 s (SILoff)
Maximum temperature coefficient: 0.01 %/K
Electrical isolation Input/output/power supply
Rated insulation voltage: 300 Vrms
Test voltage: 2.5 kV AC (50Hz, 60s)
Insulation: Safe isolation in accordance with IEC/EN61010-1
Electrical isolation Input/output
Electrical isolation: 375 V (Peak value in accordance with IEC/EN 60079-11)
Electrical isolation Input/power supply
Electrical isolation: 375 V (Peak value in accordance with IEC/EN 60079-11)
Electrical isolation Input/switching output
Electrical isolation: 375 V (Peak value in accordance with IEC/EN 60079-11)
Supply
Nominal supply voltage range: 24 V AC/DC ... 230 V AC/DC (50/60Hz)
Supply voltage range: 19.2 V AC/DC ... 253 V AC/DC (24VAC/DC...230VAC/DC (-20%...+10%, 50/60Hz))
Power consumption: < 1.5 W
Input dataSignal
Number of inputs: 1
Input signal: Temperature
Resistor
Voltage
Measurement
Sensor types (RTD) that can be used: Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC): B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range: -250°C ... 2500°C (Range depending on the sensor type)
Linear resistance measuring range: 0 Ω ... 50 kΩ
Potentiometer resistance range: 0 Ω ... 50 kΩ
Linear mV signal range: -1000 mV ... 1000 mV
Output dataSwitching: Relay
Configurable/programmable: Yes
Contact switching type: 1changeover contact
Contact material: AgSnO2, hard gold-plated
Maximum switching voltage: 30 VAC (30VDC)
Max. switching current: 0.5 A (30 V AC)
1 A (30VDC)
Signal: Current
Number of outputs: 1
Configurable/programmable: Yes
Max. voltage output signal: ± 11 V
Current output signal: 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL)
Max. current output signal: 22 mA
Load/output load voltage output: ≥ 10 kΩ
Load/output load current output: ≤ 600 Ω (20mA)
Behavior in the event of a sensor error: according to NE 43 or freely configurable
Connection dataConnection method: Push-in connection
Stripping length: 8 mm
Conductor cross section rigid: 0.2 mm² ... 1.5 mm²
Conductor cross section flexible: 0.2 mm² ... 1.5 mm²
Conductor cross section AWG: 24 ... 16
Ex dataEx installation (EPL): Gc
Div.2
SignalingError indication: Red LED
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f056408f26e75645be91508b2268a509/-S204x204-FJPG
Width: 17.5 mm
Height: 116 mm
Depth: 113.7 mm
Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715)
Material specificationsFlammability rating according to UL 94: V0 (Housing)
Housing material: PA 6.6-FR
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -20°C ... 65°C
Ambient temperature (storage/transport): -40°C ... 85°C
Permissible humidity (operation): typ. 5 % ... 95 % (non-condensing)
Altitude range (≤ 2000 m)
Altitude: ≤ 2000 m (The technical data refers to altitudes ≤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.)
Altitude range (≤ 3000 m)
Height range: > 2000 m ... 3000 m
Ambient temperature (operation): -20°C ... 55°C
Altitude range (≤ 4000 m)
Height range: > 3000 m ... 4000 m
Ambient temperature (operation): -20°C ... 50°C
Altitude range (≤ 5000 m)
Height range: > 4000 m ... 5000 m
Ambient temperature (operation): -20°C ... 45°C
ApprovalsCE
Certificate: CE-compliant
ATEX
Identification:  II 3 G Ex ec ic nC IIC T4 Gc
Certificate: PxCIF20ATEX2811378
UKCAEx(UKEX)
Identification:  II 3 G Ex ec ic nC IIC T4 Gc X
Certificate: CML 22UKEX3529X
IECEx
Identification: Ex ec ic nC IIC T4 Gc
Certificate: IECEx IBE 10.0004 X
UL, USA/Canada
Identification: UL508 Listed
Class I, Div. 2, Groups A, B, C, D T6
Class I, Zone 2, Group IIC T6
Shipbuilding approval
Certificate: DNV GL TAA000020C
Safety Integrity Level (SIL, IEC 61508)
Identification: 2
Certificate: SEBS-A.150520/17TB
Performance Level (ISO13849)
Identification: d
INMETRO
Identification: Ex ec ic nC IIC T4 Gc
Certificate: DNV 18.0143 X
EACEx
Identification:  2Ex ec ic IIC T4 Gc
Certificate: BY/112 02.01 TP012 103.01 00078
DNV GL data
Temperature: B
Humidity: B
Vibration: A
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Standards and regulationsElectrical isolation: 4-way isolation
MountingMounting type: DIN rail mounting
Technical Specs
ECLASSECLASS-11.0: 27210129
ECLASS-12.0: 27210129
ECLASS-13.0: 27210129
ETIMETIM 9.0: EC002919
UNSPSCUNSPSC 21.0: 41112100
Description
Freely programmable temperature transducer with analog output and 1 limit value relay, standard configuration, resistance thermometer in 2-, 3-, or 4-conductor technology, thermocouples, electrical isolation, wide-range power supply, Push-in connection, SIL, PL.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Application_note_00183.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_00369.pdf

Approvals_01169.pdf

Approvals_01184.pdf

Approvals_01328.pdf

Approvals_01329.pdf

Certification_00238.pdf

Certification_00254.pdf

Certification_00344.pdf

Data_sheet_03458.pdf

Manufacturer_declaration_00642.pdf

Manufacturer_declaration_01939.pdf

Manufacturer_declaration_15094.pdf

Manufacturer_declaration_17787.pdf

Manufacturer_declaration_17792.pdf

Package_slip_01571.pdf

Technical_drawing_38616.pdf