Industrial Automation
Product properties | Product type: Temperature transmitter Product family: MACX Analog Type: Signal conditioners with SIL and PL Functional Safety Configuration: DIP switches Software Insulation characteristics Overvoltage category: II Pollution degree: 2 |
Electrical properties | Electrical isolation: 4-way isolation Maximum power dissipation for nominal condition: 1.26 W Step response (0â99%): ⤠1.75 s (SILon) 1.3 s (SILoff) Maximum temperature coefficient: 0.01 %/K Electrical isolation Input/output/power supply Rated insulation voltage: 300 Vrms Test voltage: 2.5 kV AC (50Hz, 60s) Insulation: Safe isolation in accordance with IEC/EN61010-1 Electrical isolation Input/output Electrical isolation: 375 V (Peak value in accordance with IEC/EN 60079-11) Electrical isolation Input/power supply Electrical isolation: 375 V (Peak value in accordance with IEC/EN 60079-11) Electrical isolation Input/switching output Electrical isolation: 375 V (Peak value in accordance with IEC/EN 60079-11) Supply Nominal supply voltage range: 24 V AC/DC ... 230 V AC/DC (50/60Hz) Supply voltage range: 19.2 V AC/DC ... 253 V AC/DC (24VAC/DC...230VAC/DC (-20%...+10%, 50/60Hz)) Power consumption: < 1.5 W |
Input data | Signal Number of inputs: 1 Input signal: Temperature Resistor Voltage Measurement Sensor types (RTD) that can be used: Pt, Ni, Cu sensors: 2, 3, 4-wire Sensor types that can be used (TC): B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG Temperature measuring range: -250°C ... 2500°C (Range depending on the sensor type) Linear resistance measuring range: 0 é ... 50 ké Potentiometer resistance range: 0 é ... 50 ké Linear mV signal range: -1000 mV ... 1000 mV |
Output data | Switching: Relay Configurable/programmable: Yes Contact switching type: 1changeover contact Contact material: AgSnO2, hard gold-plated Maximum switching voltage: 30 VAC (30VDC) Max. switching current: 0.5 A (30 V AC) 1 A (30VDC) Signal: Current Number of outputs: 1 Configurable/programmable: Yes Max. voltage output signal: ± 11 V Current output signal: 4 mA ... 20 mA (in the case of SIL; further free configuration without SIL) Max. current output signal: 22 mA Load/output load voltage output: ⥠10 ké Load/output load current output: ⤠600 é (20mA) Behavior in the event of a sensor error: according to NE 43 or freely configurable |
Connection data | Connection method: Push-in connection Stripping length: 8 mm Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 |
Ex data | Ex installation (EPL): Gc Div.2 |
Signaling | Error indication: Red LED |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f056408f26e75645be91508b2268a509/-S204x204-FJPG Width: 17.5 mm Height: 116 mm Depth: 113.7 mm Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715) |
Material specifications | Flammability rating according to UL 94: V0 (Housing) Housing material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -20°C ... 65°C Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): typ. 5 % ... 95 % (non-condensing) Altitude range (⤠2000 m) Altitude: ⤠2000 m (The technical data refers to altitudes â¤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.) Altitude range (⤠3000 m) Height range: > 2000 m ... 3000 m Ambient temperature (operation): -20°C ... 55°C Altitude range (⤠4000 m) Height range: > 3000 m ... 4000 m Ambient temperature (operation): -20°C ... 50°C Altitude range (⤠5000 m) Height range: > 4000 m ... 5000 m Ambient temperature (operation): -20°C ... 45°C |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec ic nC IIC T4 Gc Certificate: PxCIF20ATEX2811378 UKCAEx(UKEX) Identification: ï II 3 G Ex ec ic nC IIC T4 Gc X Certificate: CML 22UKEX3529X IECEx Identification: Ex ec ic nC IIC T4 Gc Certificate: IECEx IBE 10.0004 X UL, USA/Canada Identification: UL508 Listed Class I, Div. 2, Groups A, B, C, D T6 Class I, Zone 2, Group IIC T6 Shipbuilding approval Certificate: DNV GL TAA000020C Safety Integrity Level (SIL, IEC 61508) Identification: 2 Certificate: SEBS-A.150520/17TB Performance Level (ISO13849) Identification: d INMETRO Identification: Ex ec ic nC IIC T4 Gc Certificate: DNV 18.0143 X EACEx Identification: ï 2Ex ec ic IIC T4 Gc Certificate: BY/112 02.01 TP012 103.01 00078 DNV GL data Temperature: B Humidity: B Vibration: A EMC: A Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 |
Standards and regulations | Electrical isolation: 4-way isolation |
Mounting | Mounting type: DIN rail mounting |
Description other products