Industrial Automation
Product properties | IEC test classification: I / II T1 / T2 EN type: T1 / T2 IEC power supply system: TN TT Type: Male Product type: Replacement plug Number of positions: 1 Surge protection fault message: optical Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) |
Connection data | Connection method: pluggable |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/23008288b0735347a2c6b4c9e2f0c07b/-S204x204-FJPG Width: 35.45 mm Height: 46.6 mm Depth: 56.4 mm Horizontal pitch: 2 Div. |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA 6.6/PBT Material group: I Housing material: PBT |
Protective circuit | Mode of protection: L-N L-PEN Direction of action: L-N / L-PEN Nominal voltage UN: 240VAC (TN) 240VAC (TT) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 350 VAC Nominal discharge current In (8/20) µs: 25 kA Maximum discharge current Imax (8/20) µs: 50 kA Impulse discharge current (10/350)µs, charge: 12.5 As Impulse discharge current (10/350)µs, specific energy: 160 kJ/é Impulse discharge current (10/350)µs, peak value limp: 25 kA Follow current interrupt rating Ifi: 50 kA Short-circuit current rating ISCCR: 50 kA Voltage protection level Up: ⤠1.5 kV Residual voltage Ures: ⤠1.5 kV (at In) Front of wave sparkover voltage at 6 kV (1.2/50) µs: ⤠1.5 kV TOV behavior at UT: 415 VAC (5s / withstand mode) 457 VAC (120min / withstand mode) Response time tA: ⤠100 ns Max. backup fuse with branch wiring: 315 A (gG) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 25g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
Approvals | UL specifications Maximum continuous operating voltage MCOV (L-N): 264 VAC Nominal discharge current In (L-N): 20 kA Mode of protection: L-N Nominal voltage: 240VAC Power distribution system: Split phase Nominal frequency: 50/60 Hz Measured limiting voltage MLV (L-N): 1350 V Follow current (L-N): 10 kA (264 VAC) SPD Type: 4CA |
Standards and regulations | Air clearances and creepage distances Standards/regulations: EN60664-1 / IEC 60664-1 / IEC 61643-11 Standards/specifications: IEC 61643-11 EN61643-11 Note: 2011 2012 |
Mounting | Mounting type: on base element |
ECLASS | ECLASS-11.0: 27130802 ECLASS-13.0: 27171201 |
ETIM | ETIM 9.0: EC000381 |
UNSPSC | UNSPSC 21.0: 39121600 |
Description other products