PHOENIX CONTACT 2864273
PHOENIX CONTACTNot available

MINI MCR-SL-PT100-UI-NC - Resistance thermometer measuring transducer

MCR temperature transducer for Pt100 temperature sensors, configured via DIP switches, with screw connection, not preconfigured
Product Code: 2864273
Partner cod.: 2864273
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
NotesUtilization restriction
EMC note: EMC: class A product, see manufacturer's declaration in the download area
Product propertiesProduct type: Temperature transmitter
Product family: MINI Analog
No. of channels: 1
Configuration: DIP switches
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
Electrical propertiesNo. of channels: 1
Electrical isolation: 3-way isolation
Maximum power dissipation for nominal condition: 235.5 mW
Protective circuit: Transient protection
Step response (0–99%): < 160 ms
Maximum temperature coefficient: < 0.02 %/K
Transmission error in the set measuring range: ((100 K / set measurement range [K]) + 0.1)%
Transmission error in the full measuring range: ≤0,2%
Electrical isolation Input/output/power supply
Rated insulation voltage: 50 V AC/DC
Test voltage: 1.5 kV AC (50Hz, 60s)
Insulation: Basic insulation in accordance with IEC/EN61010
Supply
Nominal supply voltage: 24 VDC
Supply voltage range: 19.2 VDC ... 30 VDC (The DIN rail connector (ME 6,2 TBUS-2 1,5/5-ST-3,81 GN, item no. 2869728) can be used to bridge the supply voltage. It can be snapped onto a 35 mm DIN rail in accordance with EN60715)
Max. current consumption: < 21 mA (at 24 V DC)
Power consumption: < 500 mW
Input dataSignal
Number of inputs: 1
Measurement
Configurable/programmable: Yes
Sensor types (RTD) that can be used: Pt 100 (IEC 60751/EN 60751)
Temperature measuring range: min. 50 K
Sensor type:: -150°C ... 850°C (configurable)
Sensor input current: 1 mA (constant)
Max. permissible overall conductor resistance: 10 Ω (Per cable)
Connection technology: 2-, 3-, 4-conductor
Output dataSignal: Voltage/current
Number of outputs: 1
Configurable/programmable: Yes, unconfigured
Voltage output signal: 0 V ... 5 V
1 V ... 5 V
0 V ... 10 V
10 V ... 0 V
Max. voltage output signal:  12.5 V
Non-load voltage:  12.5 V
Current output signal: 0 mA ... 20 mA
4 mA ... 20 mA
20 mA ... 0 mA
20 mA ... 4 mA
Max. current output signal: 23 mA
Short-circuit current:  10 mA
Load/output load voltage output: ≥ 10 kΩ
Load/output load current output: < 500 Ω (at 20 mA)
Ripple: < 20 mVPP (at 10 kΩ)
< 20 mVPP (at 500 Ω)
Connection dataConnection method: Screw connection
Stripping length: 12 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 26 ... 12
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/8450693c9d67004aa7841c306225c8da/-S204x204-FJPG
Width: 6.2 mm
Height: 93.1 mm
Depth: 101.2 mm
Material specificationsFire protection for rail vehicles (DIN EN 45545-2) R22: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R23: HL 1 - HL 2
Fire protection for rail vehicles (DIN EN 45545-2) R24: HL 1 - HL 2
Housing material: PBT
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -20°C ... 65°C
Ambient temperature (storage/transport): -40°C ... 85°C
Altitude: ≤ 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
ApprovalsCE
Certificate: CE-compliant
UKCA
Certificate: UKCA-compliant
UL, USA/Canada
Identification: UL508 Recognized
Class I, Div. 2, Groups A, B, C, D T5
Shipbuilding approval
Certificate: DNV GL TAA00002R0
DNV GL data
Temperature: B
Humidity: B
Vibration: B
EMC: A
Enclosure: Required protection according to the Rules shall be provided upon installation on board
EMC dataNoise immunity: EN 61000-6-2
Note: When being exposed to interference, there may be minimal deviations.
Electromagnetic compatibility: Conformance with EMC directive
Noise emission: EN 61000-6-4
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Comments: Safety measures must be taken to prevent electrostatic discharge.
Electromagnetic HF field
Designation: Electromagnetic RF field
Standards/regulations: EN61000-4-3
Typical deviation from the measuring range final value: 10 %
Fast transients (burst)
Designation: Fast transients (burst)
Standards/regulations: EN61000-4-4
Typical deviation from the measuring range final value: 10 %
Surge current load (surge)
Standards/regulations: EN61000-4-5
Surge current load (surge)​
Comments: Criterion B
Conducted interference
Designation: Conducted interferences
Standards/regulations: EN61000-4-6
Typical deviation from the measuring range final value: 10 %
Standards and regulationsElectrical isolation: 3-way isolation
MountingMounting type: DIN rail mounting
Assembly instructions: The DIN rail connector can be used for bridging the supply voltage. It can be snapped onto a 35mm EN60715 DIN rail.
Mounting position: any
Technical Specs
ECLASSECLASS-11.0: 27210129
ECLASS-12.0: 27210129
ECLASS-13.0: 27210129
ETIMETIM 9.0: EC002919
UNSPSCUNSPSC 21.0: 41112100
Description
MCR temperature transducer for Pt 100 temperature sensors, configured via DIP switch, with screw connection, not pre-configured
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01435.pdf

Approvals_01560.pdf

Approvals_01561.pdf

Data_sheet_03575.pdf

Manual_00026.pdf

Manufacturer_declaration_00565.pdf

Manufacturer_declaration_02360.pdf

Manufacturer_declaration_15263.pdf

Package_slip_01659.pdf

Product_information_00033.pdf

Product_information_00459.pdf

Technical_drawing_38973.pdf