Industrial Automation
Notes | Utilization restriction EMC note: EMC: class A product, see manufacturer's declaration in the download area |
Product properties | Product type: Power module Product family: MACX Analog Insulation characteristics: GBStandard Overvoltage category: II Pollution degree: 2 |
Electrical properties | Electrical isolation Supply/switching output Electrical isolation: 50 V AC/DC |
Input data | Signal Voltage input signal: 19.2 VDC ... 30 VDC (24VDC, -20%...+25%) Fuse: 5 A (replaceable), slow-blow 250 V AC Polarization and surge protection: Yes |
Output data | Switching: Relay Contact switching type: 1changeover contact Contact material: Gold (Au) Maximum switching voltage: 50 VAC (2A) 30 VDC (2A) 50 VDC (0.22A) Signal Max. current output signal: 3.75 A Output voltage: Input voltage - max 0.8 V at 3.75 A |
Connection data | Connection method: Screw connection Stripping length: 7 mm Screw thread: M3 Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section AWG: 24 ... 14 Tightening torque: 0.5 Nm ... 0.6 Nm |
Ex data | Ex installation (EPL): Gc Div.2 |
Signaling | Status display: 1 x red LED (error) 2 x green LEDs (PWR1 and PWR2) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/f056408f26e75645be91508b2268a509/-S204x204-FJPG Width: 17.5 mm Height: 103.6 mm Depth: 113.7 mm Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715) |
Material specifications | Flammability rating according to UL 94: V0 (Housing) Housing material: Polyamide (PA 6.6) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 (not assessed by UL) Ambient temperature (operation): -40°C ... 60°C (Any mounting position) Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m Permissible humidity (operation): 5 % ... 95 % (non-condensing) |
Approvals | CE Certificate: CE-compliant ATEX Identification: ï II 3 G Ex ec nC IIC T4 Gc X Certificate: PxCIF08ATEX2865625X UKCAEx(UKEX) Identification: ï II 3 G Ex nA nC IIC T4 Gc X Certificate: PxCIF21UKEX2865625X IECEx Identification: Ex ec nC IIC T4 Gc Certificate: IECEx IBE 08.0004X CCC/China-Ex Identification: Ex ec nC IIC T4 Gc Certificate: 2021122303114198 UL, USA/Canada Identification: UL 61010 Listed Class I, Div. 2, Groups A, B, C, D T5 Class I, Zone 2, Group IIC Shipbuilding approval Certificate: DNV GL TAA00000AG EACEx Identification: ï 2Ex ec nC IIC T4 Gc Certificate: BY/112 02.01 TP012 103.01 00078 DNV GL data Temperature: B Humidity: B Vibration: A EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 Electromagnetic HF field Designation: Electromagnetic RF field Standards/regulations: EN61000-4-3 Evaluation criterion: A Fast transients (burst) Designation: Fast transients (burst) Standards/regulations: EN61000-4-4 Evaluation criterion: A Conducted interference Designation: Conducted interferences Standards/regulations: EN61000-4-6 Evaluation criterion: A |
Standards and regulations | GBStandard Standards/regulations: GB3836.1 GB3836.3 GB3836.8 |
Mounting | Mounting type: DIN rail mounting |
ECLASS | ECLASS-11.0: 27242610 ECLASS-12.0: 27242610 ECLASS-13.0: 27242610 |
ETIM | ETIM 9.0: EC001600 |
UNSPSC | UNSPSC 21.0: 32151600 |