Industrial Automation
Product properties | Product type: Extension module MTTF: 1249 Years (SN29500 standard, temperature25°C, operating cycle21%) 506 Years (SN29500 standard, temperature40°C, operating cycle34.25%) 194 Years (SN29500 standard, temperature40°C, operating cycle100%) Insulation characteristics Overvoltage category: II Degree of pollution: 2 |
Electrical properties | Rated insulation voltage: 60 V (In accordance with EN/IEC 60079-7) Electrical isolation: 50 V (Rated insulation voltage (in each case between the Pt 100 inputs / TBUS supply, reinforced insulation in accordance with EN61010)) 300 V (Rated insulation voltage (to adjacent devices, basic insulation in accordance with EN/IEC 61010)) Test voltage: 1.5 kV AC (50Hz, 1min.) Maximum power dissipation for nominal condition: 0.912 W Transient surge protection: Yes Supply Supply voltage range: 19.2 VDC ... 30.5 VDC (DIN rail connector) Max. current consumption: ⤠38 mA (At 24 V DC, at 25°C) |
Input data | Analog Description of the input: Pt100 input Number of inputs: 4 Connection technology: 2-, 3-conductor Temperature measuring range: -50°C ... 250°C Measuring accuracy: 0.1% (From the measuring range final value) Process data channel: 16 bit (per channel) Max. permissible overall conductor resistance: 25 é Sensor input current: 1 mA (constant) |
Connection data | Tightening torque: 0.5 Nm ... 0.6 Nm 5 lbf-in. ... 7 lbf-in. Connection method: Screw connection Stripping length: 7 mm Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 2.5 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 2.5 mm² Conductor cross section AWG min.: 24 Conductor cross section AWG max.: 14 |
Signaling | Status display: Green LED (supply voltage, PWR) Green LED (bus communication, DAT) Red LED (periphery error, ERR) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/2cf50fa12a76e642a87bbf025fee56a1/-S204x204-FJPG Width: 17.5 mm Height: 113 mm Depth: 114.5 mm |
Material specifications | Material: PA 6.6-FR Flammability rating according to UL 94: V0 |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C -40°F ... 158°F Ambient temperature (storage/transport): -40°C ... 85°C -40°F ... 185°F Altitude: 2000 m Permissible humidity (operation): 20 % ... 85 % Permissible humidity (storage/transport): 20 % ... 85 % Shock: 16g, 11 ms Vibration (operation): in accordance with IEC 60068-2-6: 5g, 10 Hz ... 150 Hz |
Approvals | CE Certificate: CE-compliant UKCA Certificate: UKCA-compliant ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: IBExU15ATEXB008X Note: Please follow the special installation instructions in the documentation! IECEx Identification: Ex ec IIC T4 Gc Certificate: IECExIBE13.0019X EACEx Identification: 2Ex nA nC IIC T4 Gc X Certificate: RU C-DE.HB49.B.00033/20 UL, USA/Canada Identification: 508 Listed Class I, Div. 2, Groups A, B, C, D T4A Class I, Zone 2, IIC T4 CCC/China-Ex Identification: Ex ec IIC T4 Gc Certificate: 2022122310115625 KC-s Certificate: KTL 20-KA4BO-149X Corrosive gas test Identification: ISA-S71.04-1985 G3 Harsh Group A |
EMC data | Noise immunity: EN 61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Noise emission: EN 61000-6-4 |
Standards and regulations | Standard designation: EMC Directive 2014/30/EU Ex Directive (ATEX) Ex Directive (ATEX) Standards/specifications: EN61000-6-2 EN61000-6-4 EN60079-0 EN60079-15 |
Mounting | Assembly instructions: on standard DIN rail NS 35 in accordance with EN 60715 Mounting position: any |
ECLASS | ECLASS-11.0: 27242601 ECLASS-12.0: 27242601 ECLASS-13.0: 27242601 |
ETIM | ETIM 9.0: EC001596 |
UNSPSC | UNSPSC 21.0: 32151602 |
Description other products