Industrial Automation
FLT-SEC-T1-350/25-P - Type 1/2 surge protection plug
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
![](https://www.technologybsa.com/wp-content/uploads/2023/08/copia.png)
Notes | General Note: Only in parallel connection with VAL-SEC-T2-350-P. The technical parameters are based on the combination of the two products. |
Product properties | IEC test classification: I / II I T1 / T2 T1 EN type: T1 / T2 IEC power supply system: TN TT Type: Male Product type: Replacement plug Product family: SEC Family Number of positions: 1 Surge protection fault message: optical Insulation characteristics Overvoltage category: III Pollution degree: 2 |
Electrical properties | Nominal frequency fN: 50 Hz (60Hz) |
Connection data | Connection method: pluggable |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/59a3473422fd3e4f9c77f55fafc495ea/-S204x204-FJPG Width: 23.5 mm Height: 46.4 mm Depth: 59.4 mm Horizontal pitch: 2 Div. |
Material specifications | Flammability rating according to UL 94: V-0 CTI value of material: 600 Insulating material: PA6.6-FR 20% GF PBT-FR Material group: I Housing material: PA 6.6-FR 20% GF PBT-FR |
Protective circuit | Mode of protection: L-N L-PEN Direction of action: L-N / L-PEN Nominal voltage UN: 240VAC (TN) 240VAC (TT) Nominal frequency fN: 50 Hz (60Hz) Maximum continuous voltage UC: 350 VAC Nominal discharge current In (8/20) µs: 25 kA Impulse discharge current (10/350)µs, charge: 12.5 As Impulse discharge current (10/350)µs, specific energy: 160 kJ/é Impulse discharge current (10/350)µs, peak value limp: 25 kA Follow current interrupt rating Ifi: 25 kA (264 V AC) 3 kA (350 V AC) Short-circuit current rating ISCCR: 25 kA (264 V AC) 3 kA (350 V AC) Voltage protection level Up: ⤠1.5 kV Residual voltage Ures: ⤠1.5 kV (at In) ⤠1.2 kV (at 10 kA) ⤠1 kV (at 5 kA) ⤠0.9 kV (at 3kA) Front of wave sparkover voltage at 6 kV (1.2/50) µs: ⤠1.5 kV TOV behavior at UT: 415 VAC (5s / withstand mode) 457 VAC (120min / safe failure mode) Response time tA: ⤠25 ns Max. backup fuse with branch wiring: 315 A (gG) Additional technical data Maximum discharge current Imax (8/20) µs: 100 kA |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 80°C Ambient temperature (storage/transport): -40°C ... 80°C Altitude: ⤠2000 m (amsl) Permissible humidity (operation): 5 % ... 95 % Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z) Vibration (operation): 5g (5 - 500 Hz/2.5 h/X, Y, Z) |
Approvals | UL specifications Maximum continuous operating voltage MCOV: 264 VAC Short-circuit current rating (SCCR): 50 kA Voltage protection rating VPR: 1200 V Nominal discharge current In: 20 kA Mode of protection: L-N L-G Nominal voltage: 240VAC Power distribution system: Single phase Nominal frequency: 50/60 Hz SPD Type: 1CA |
Standards and regulations | Standards/specifications: IEC 61643-11 Note: 2011 EN 61643-11 Standards/specifications: EN61643-11 Note: 2012 |
Mounting | Mounting type: on base element |
ECLASS | ECLASS-11.0: 27130890 ECLASS-13.0: 27171292 |
ETIM | ETIM 9.0: EC002496 |
UNSPSC | UNSPSC 21.0: 39121600 |
Description other products