Industrial Automation
Product properties | Product type: Output signal conditioner Product family: MACX Analog No. of channels: 2 Type: Signal conditioners with SIL functional safety |
Electrical properties | No. of channels: 2 Electrical isolation: 4-way isolation Signal transmission behavior: In=Out Step response (10-90%): < 140 µs (for 4 mA ... 20 mA step) Maximum temperature coefficient: 0.01 %/K Temperature coefficient, typical: ⤠0.005 %/K Maximum transmission error: 0.1 % (of final value) Transmission error, typical: ⤠0.05 % (of final value) Electrical isolationâ Overvoltage category: II Pollution degree: 2 Electrical isolation Input/output IEC/EN61010-1 Standards/regulations: IEC/EN61010-1 Rated insulation voltage: 300 Vrms Test voltage: 2.5 kV AC (50Hz, 60s) Insulation: Safe isolation Electrical isolation Input/power supply IEC/EN61010-1 Standards/regulations: IEC/EN61010-1 Rated insulation voltage: 50 Vrms Test voltage: 1.5 kV AC (50Hz, 60s) Insulation: Basic insulation Electrical isolation Output/supply IEC/EN61010-1 Standards/regulations: IEC/EN61010-1 Rated insulation voltage: 300 Vrms Test voltage: 2.5 kV AC (50Hz, 60s) Insulation: Safe isolation Electrical isolation Input1/input2, output1/output2 Test voltage: 1.5 kV AC (50Hz, 60s) Supply Nominal supply voltage: 24 VDC -20%...+25% Supply voltage range: 19.2 VDC ... 30 VDC Max. current consumption: < 85 mA (24VDC / 20mA) Power dissipation: < 1.4 W (24VDC / 20mA) Power consumption: ⤠2 W (24VDC / 20mA) |
Input data | Signal: Current Current input signal: 0.2 mA ... 20 mA (Function) 4 mA ... 20 mA (Safety) 0 mA ... 24 mA (Underload/overload range) Input current: ⤠30 mA Input impedance: > 1 Mé (If there is a line fault) Line fault detection: > 0.2 mA (Response threshold of input current) Voltage drop: < 2.4 V (at 20 mA) |
Output data | Signal: Current Number of outputs: 2 Current output signal: 0.2 mA ... 20 mA (Function) 4 mA ... 20 mA (Safety) 0 mA ... 24 mA (Underload/overload range) Load: 100 é ... 700 é (20mA) 100 é ... 650 é (20.5mA) 100 é ... 500 é (24mA) Output ripple: < 20 mVrms Non-load voltage: ⤠27 V Line fault detection: > 10 ké (Line break) < 50 é (Short circuit) |
Connection data | Connection method: Push-in connection Stripping length: 10 mm Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross section flexible (2 conductors with same cross section): 0.25 mm² ... 0.34 mm² (TWIN ferrule without plastic sleeve) 0.5 mm² ... 1.5 mm² (TWIN ferrule with plastic sleeve) Conductor cross section AWG: 24 ... 14 24 ... 22 (TWIN ferrule without plastic sleeve) 20 ... 16 (TWIN ferrule with plastic sleeve) |
Ex data | Ex installation (EPL): Gc Div.2 |
Interfaces | Data communication (bypass) HART function: Yes Protocols supported: HART-transparent |
Signaling | Status display: Green LED (supply voltage) |
Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/3edd36290ae8094db8e0add7aa964a6f/-S204x204-FJPG Width: 12.5 mm Height: 107.9 mm Depth: 113.7 mm Depth NS35/7,5: 114.5 mm (Snapped onto DIN rail NS35/7,5 in accordance with EN60715) |
Material specifications | Flammability rating according to UL 94: V0 (Housing) Housing material: PA 6.6-FR |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -40°C ... 70°C (Any mounting position) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Altitude range (⤠2000 m (Ex)) Description: Ex applications Altitude: ⤠2000 m (The technical data refers to altitudes â¤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.) Ambient temperature (operation): -40°C ... 70°C Rated insulation voltage: 320 V (Power supply, input / output) Altitude range (⤠3000 m (Ex)) Description: Ex applications Height range: > 2000 m ... 3000 m Ambient temperature (operation): -40°C ... 60°C Rated insulation voltage: 190 V (Power supply, input / output) Altitude range (⤠4000 m (Ex)) Description: Ex applications Height range: > 3000 m ... 4000 m Ambient temperature (operation): -40°C ... 55°C Rated insulation voltage: 63 V (Power supply, input / output) Altitude range (⤠5000 m (Ex)) Description: Ex applications Height range: > 4000 m ... 5000 m Ambient temperature (operation): -40°C ... 45°C Rated insulation voltage: 63 V (Power supply, input / output) Altitude range (⤠2000 m) Description: Non-Ex applications (EN61010-1) Altitude: ⤠2000 m (The technical data refers to altitudes â¤2000m above mean sea level. For altitudes >2000m above mean sea level, refer to the data sheet.) Ambient temperature (operation): -40°C ... 70°C Rated insulation voltage: 300 V (Power supply, input / output) Altitude range (⤠3000 m) Description: Non-Ex applications (EN61010-1) Height range: > 2000 m ... 3000 m Ambient temperature (operation): -40°C ... 60°C Rated insulation voltage: 150 V (Power supply, input / output) Altitude range (⤠4000 m) Description: Non-Ex applications (EN61010-1) Height range: > 3000 m ... 4000 m Ambient temperature (operation): -40°C ... 55°C Rated insulation voltage: 150 V (Power supply, input / output) Altitude range (⤠5000 m) Description: Non-Ex applications (EN61010-1) Height range: > 4000 m ... 5000 m Ambient temperature (operation): -40°C ... 45°C Rated insulation voltage: 150 V (Power supply, input / output) |
Approvals | CE Certificate: CE-compliant Note: and EN61326 ATEX Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: BVS 20 ATEX E 003 X UKCAEx(UKEX) Identification: ï II 3 G Ex ec IIC T4 Gc Certificate: PxCIF21UKEx2908065X IECEx Identification: Ex ec IIC T4 Gc Certificate: IECEx BVS 20.0003X CCC/China-Ex Identification: Ex ec IIC T4 Gc Certificate: 2021122304114079 UL, USA/Canada Identification: UL 61010 Listed Class I, Div. 2, Groups A, B, C, D T4 Class I, Zone 2, Group IIC T4 Shipbuilding approval Certificate: DNV GL TAA00000AG Safety Integrity Level (SIL, IEC 61508) Identification: 3 Systematic Capability Identification: 3 INMETRO Identification: Ex ec IIC T4 Gc Certificate: DNV 21.0092 X EAC Identification: 2Ex e IIC T4 Gc X Certificate: RU C-DE.HB49.B.00145/21 DNV GL data Temperature: B Humidity: B Vibration: A EMC: B Enclosure: Required protection according to the Rules shall be provided upon installation on board |
EMC data | Noise immunity: EN 61000-6-2 Note: When being exposed to interference, there may be minimal deviations. Electromagnetic compatibility: Conformance with EMC directive Noise emission: EN 61000-6-4 |
Standards and regulations | Electrical isolation: 4-way isolation GBStandard Standards/regulations: GB/T3836.1 GB/T3836.3 |
Mounting | Mounting type: DIN rail mounting |
Description other products