Industrial Automation

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Design Software

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2909635
PHOENIX CONTACT 2909635
PHOENIX CONTACTNot available

VAL-SEC-T2-3S-350/40-FM - Type 2 surge arrester

Pluggable surge protective device, in accordance with Type 2/Class II, for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), with remote indication contact. With 40 kA discharge capacity in accordance with the requirements of VDE 0100-534:2016-10 relating to SPDs at the system feed point.
Product Code: 2909635
Partner cod.: 2909635
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Technical Specs
Description
Download
Tecnichal data
Product propertiesIEC test classification: II
T2
EN type: T2
IEC power supply system: TN-S
TT
Type: DIN rail module, two-section, divisible
Product type: Surge arrester
Product family: SEC Family
Number of positions: 4
Surge protection fault message: Optical, remote indicator contact
Insulation characteristics
Overvoltage category: III
Pollution degree: 2
Electrical propertiesNominal frequency fN: 50 Hz (60Hz)
Indicator/remote signaling
Connection name: Remote fault indicator contact
Switching function: Changeover contact
Operating voltage: 5 VAC ... 250 VAC
125 VDC (200 mA DC)
Operating current: 5 mA AC ... 1 A AC
1 ADC (30VDC)
Connection dataConnection method: Screw connection
Fork-type cable lug
Screw thread: M5
Tightening torque: 4.5 Nm
Stripping length: 16 mm
Conductor cross section flexible: 2.5 mm² ... 16 mm²
1.5 mm² ... 6 mm²
Conductor cross section rigid: 2.5 mm² ... 25 mm²
Conductor cross section AWG: 12 ... 4
Remote fault indicator contact
Connection method: Plug-in/screw connection via COMBICON
Screw thread: M2
Tightening torque: 0.25 Nm
Stripping length: 7 mm
Conductor cross section flexible: 0.14 mm² ... 1.5 mm²
Conductor cross section rigid: 0.14 mm² ... 1.5 mm²
Conductor cross section AWG: 28 ... 16
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/ebaf2b9bc5be9b47b616da0efe0474eb/-S204x204-FJPG
Width: 49.2 mm
Height: 97.9 mm
Depth: 74.5 mm (incl. DIN rail 7.5mm)
Horizontal pitch: 2.7 Div.
Material specificationsFlammability rating according to UL 94: V-0
CTI value of material: 600
Insulating material: PA6.6-FR 20% GF
PBT-FR
Material group: I
Housing material: PA 6.6-FR 20% GF
PBT-FR
Protective circuitMode of protection: L-N
L-PE
N-PE
Direction of action: 3L-N & N-PE
Nominal voltage UN: 240/415VAC (TN-S)
240/415VAC (TT)
Nominal frequency fN: 50 Hz (60Hz)
Maximum continuous operating voltage UC (L-N): 350 VAC
Maximum continuous operating voltage UC (L-PE): 350 VAC
Maximum continuous operating voltage UC (N-PE): 264 VAC
Rated load current IL: 40 A (Biconnect M4 fork-type cable lug 6​ mm²)
63 A (TWIN ferrule 2 x 10 mm²)
Residual current IPE: ≤ 1 µA
Nominal discharge current In (8/20) µs (L-N): 20 kA
Nominal discharge current In (8/20) µs (L-PE): 20 kA
Nominal discharge current In (8/20) µs (N-PE): 40 kA
Maximum discharge current Imax (8/20) µs (L-N): 40 kA
Maximum discharge current Imax (8/20) µs (L-PE): 40 kA
Maximum discharge current Imax (8/20) µs (N-PE): 80 kA
Follow current interrupt rating Ifi (N-PE): 100 A (264 V AC)
Short-circuit current rating ISCCR: 25 kA (for a backup fuse of up to 315AgG)
50 kA (for a backup fuse of up to 200AgG)
Voltage protection level Up (L-N): ≤ 1.5 kV
Voltage protection level Up (L-PE): ≤ 1.9 kV
Voltage protection level Up (N-PE): ≤ 1.5 kV
Residual voltage Ures (L-N): ≤ 1.5 kV (at In)
≤ 1.3 kV (at 10 kA)
≤ 1.2 kV (at 5 kA)
≤ 1.1 kV (at 4 kA)
≤ 1 kV (at 2 kA)
Residual voltage Ures (N-PE): ≤ 0.7 kV (at In)
≤ 0.7 kV (at 20 kA)
≤ 0.7 kV (at 8kA)
≤ 0.7 kV (at 4 kA)
TOV behavior at UT (L-N): 415 VAC (5s / withstand mode)
457 VAC (120min / safe failure mode)
TOV behavior at UT (N-PE): 1200 VAC (200ms / withstand mode)
Response time tA (L-N): ≤ 25 ns
Response time tA (L-PE): ≤ 100 ns
Response time tA (N-PE): ≤ 100 ns
Max. backup fuse with V-type through wiring: 40 A (gG / Biconnect M4 fork-type cable lug, 6​ mm²)
63 A (gG / TWIN ferrule 2x 10mm²)
Max. backup fuse with branch wiring: 315 A (gG)
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 80°C
Ambient temperature (storage/transport): -40°C ... 80°C
Altitude: ≤ 2000 m (amsl)
Permissible humidity (operation): 5 % ... 95 %
Shock (operation): 30g (Half-sine / 11 ms / 3x ±X, ±Y, ±Z)
Vibration (operation): 5g (10 ... 500 Hz / 2.5 h / X, Y, Z)
Standards and regulationsStandards/specifications: IEC 61643-11
Note: 2011
EN 61643-11
Standards/specifications: EN61643-11
Note: 2012
MountingMounting type: DIN rail: 35 mm
Technical Specs
ECLASSECLASS-11.0: 27130805
ECLASS-13.0: 27171202
ETIMETIM 9.0: EC000941
UNSPSCUNSPSC 21.0: 39121600
Description
Pluggable surge protective device, in accordance with Type 2/Class II, for 3-phase power supply networks with separate N and PE (5-conductor system: L1, L2, L3, N, PE), with remote indication contact. With 40 kA discharge capacity in accordance with the requirements of VDE 0100-534:2016-10 relating to SPDs at the system feed point.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00343.pdf

Approvals_01875.pdf

Flyer_00001.pdf

Flyer_00002.pdf

Flyer_00003.pdf

Manufacturer_declaration_00786.pdf

Manufacturer_declaration_02098.pdf

Package_slip_00568.pdf

Technical_drawing_40809.pdf