Industrial Automation
Product properties | Product type: Safety relays Product family: PSRclassic Application: Emergency stop Safety door Light grid Mechanical service life: 10x 106 cycles Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/EN61810-3 |
Electrical properties | Maximum power dissipation for nominal condition: 3.6 W Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VAC Rated surge voltage/insulation: Basic insulation 4kV: between all current paths and housing Safe isolation, reinforced insulation 6kV: between 13/14, 23/24, 33/34, and the remaining current paths between 13/14, 23/24, 33/34 among one another Supply Rated control circuit supply voltage US: 20.4 VDC ... 26.4 VDC 24 VDC -15% / +10% |
Input data | General Power consumption at US: typ. 3.6 W Rated control supply current IS: typ. 150 mA Inrush current: 200 mA (at US) < 40 mA (with Us/Ix to S10) < 150 mA (with Us/Ix to S12) > -60 mA (with Us/Ix to S22) < 40 mA (with Us/Ix to S34) < 40 mA (with Us/Ix to S35) Current consumption: < 40 mA (with Us/Ix to S10) < 40 mA (with Us/Ix to S12) > -40 mA (with Us/Ix to S22) 0 mA (with Us/Ix to S34) < 5 mA (with Us/Ix to S35) Voltage at input/start and feedback circuit: 24 VDC -15% / +10% Filter time: 1 ms (at A1 in the event of voltage dips at Us) max. 1.5 ms (at S10, S12; test pulse width) 7.5 ms (at S10, S12; test pulse rate) Test pulse rate=5xTest pulse width Typical response time: < 600 ms (automatic start) < 70 ms (manual start) Typ. starting time with Us: < 600 ms (when controlled via A1) Typical release time: < 20 ms (when controlled via S11/S12 and S21/S22) < 20 ms (when controlled via A1) Concurrence: â Recovery time: < 1 s Delay time: K3(t), K4(t) fixed depending on model Maximum switching frequency: 0.5 Hz Protective circuit: Surge protection; Suppressor diode Max. permissible overall conductor resistance: approx. 11 é (Input and start circuits at US) Operating voltage display: 1 x green LED Status display: 4 x green LEDs |
Output data | Contact switching type: 5 enabling current paths 1 signaling current path Contact material: AgSnO2 Maximum switching voltage: 250 V AC/DC (Observe the load curve) Minimum switching voltage: 5 V AC/DC Limiting continuous current: 6 A (N/O contact, pay attention to the derating) 6 A (N/C contact) Maximum inrush current: 20 A (Ãtï£100ms, undelayed contacts) 8 A (delayed contacts) Inrush current, minimum: 10 mA Sq. Total current: 55 A2 (observe derating) Interrupting rating (ohmic load) max.: 144 W (24 V DC, à = 0 ms) 288 W (48 V DC, à = 0 ms) 110 W (110 V DC, à = 0 ms, delayed contacts: 77W) 88 W (220 V DC, à = 0 ms) 1500 VA (250 V AC, à = 0 ms, delayed contacts: 2000VA) Maximum interrupting rating (inductive load): 42 W (24 V DC, à = 40 ms, delayed contacts: 48W) 42 W (48 V DC, à = 40 ms, delayed contacts: 40W) 42 W (110 V DC, à = 40 ms, delayed contacts: 35W) 42 W (220 V DC, à = 40 ms, delayed contacts: 33W) Switching capacity min.: 50 mW Switching capacity (360/h cycles): 4 A (24VDC) 4 A (230 V AC) Switching capacity (3600/h cycles): 2.5 A (24V (DC13)) 3 A (230 V (AC15)) Output fuse: 10 A gL/gG (N/O contact) 6 A gL/gG (N/C contact) |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible, with ferrule, with plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross section flexible, with ferrule without plastic sleeve: 0.25 mm² ... 1.5 mm² (only together with CRIMPFOX 6) Conductor cross-section AWG: 24 ... 16 Stripping length: 8 mm |
Dimensions | Width: 45 mm Height: 112 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 1 Safety data: ENISO13849 Category: 4 (Undelayed contacts) 3 (delayed contacts) Performance level (PL): e (for delayed contacts PLd) Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 3 (for delayed contacts SIL2) Safety data: IEC 61508 - Low demand Safety Integrity Level (SIL): 3 (for delayed contacts SIL2) Safety data: ENIEC 62061 Safety Integrity Level (SIL): 3 (for delayed contacts SIL2) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -20°C ... 55°C (observe derating) Ambient temperature (storage/transport): -40°C ... 70°C Maximum altitude: ⤠2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g Vibration (operation): 10Hz...150Hz, 2g |
Approvals | CE Certificate: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: DINEN50178/VDE0160 |
Mounting | Mounting type: DIN rail mounting Mounting position: any Connection method: Push-in connection |
ECLASS | ECLASS-11.0: 27371819 ECLASS-13.0: 27371819 ECLASS-12.0: 27371819 |
ETIM | ETIM 9.0: EC001449 |
UNSPSC | UNSPSC 21.0: 39122200 |
Description other products