Industrial Automation
PSR-SCP- 24DC/FSP2/2X1/1X2 - Coupling relay


Product properties | Product type: Coupling relay Product family: PSRclassic Application: Safe switch off High demand Low demand Mechanical service life: 10x 106 cycles Relay type: Electromechanical relay with force-guided contacts in accordance with IEC/ENÃ61810-3 |
Electrical properties | Maximum power dissipation for nominal condition: 2.4 W Nominal operating mode: 100% operating factor Air clearances and creepage distances between the power circuits Rated insulation voltage: 250 VÃAC Rated surge voltage/insulation: Safe isolation, reinforced insulation 6ÃkV between the control circuits (A1/A2), (31/32), (13/14, 23/24) |
Input data | General Rated control circuit supply voltage US: 24 VÃDC -15Ã% / +10Ã% Power consumption at US: typ. 1.32 W Rated control supply current IS: typ. 55 mA Input voltage range: 20.4 VÃDC ... 26.4 VÃDC Inrush current: max. 100 mA Filter time: max. 5 ms (at A1 in the event of voltage dips at Us) max. 2 ms (Test pulse width; high test pulse at A1/A2) ââ°¥ 100 ms (Test pulse width; high test pulse at A1/A2) Test pulse rateÃ=Ã80ÃxÃTest pulse width max. 5 ms (Test pulse width; low test pulse at A1/A2) ââ°¥ 50 ms (Test pulse rate; low test pulse at A1/A2) Test pulse rateÃ=Ã15ÃxÃTest pulse width Typ. starting time with Us: 50 ms Typical release time: 50 ms Recovery time: 1 s Maximum switching frequency: 0.5 Hz Protective circuit: Surge protection; Suppressor diode, 33 V (A1 - A2) Operating voltage display: 1 x yellow LED |
Output data | Contact switching type: 2 enabling current paths 1 confirmation current path Contact material: AgCuNi, + 0.2Ãõm Au Maximum switching voltage: 250 V AC/DC (N/O contact / N/C contact, observe the load curve) Minimum switching voltage: 15 V AC/DC (N/O contact / N/C contact) Limiting continuous current: 5 A (N/O contact, pay attention to the derating) 100 mA (N/C contact) Maximum inrush current: 5 A (N/O contact) 100 mA (N/C contact) Inrush current, minimum: 5 mA (N/O contact / N/C contact) Sq. Total current: 50 A2 (observe derating) Interrupting rating (ohmic load) max.: 120 W (24 V DC, Ãâ = 0 ms, N/C contact: 2.4 W) 192 W (48 V DC, Ãâ = 0 ms, N/C contact: 4.8 W) 162 W (60 V DC, Ãâ = 0 ms, N/C contact: 6 W) 66 W (110 V DC, Ãâ = 0 ms, N/C contact: 11 W) 60 W (220 V DC, Ãâ = 0 ms, N/C contact: 22 W) 1250 VA (250 V AC, Ãâ = 0 ms, N/C contact: 25 VA) Maximum interrupting rating (inductive load): 72 W (24 V DC, Ãâ = 40 ms, N/C contact: 2.4 W) 43 W (48 V DC, Ãâ = 40 ms, N/C contact: 4.8 W) 41 W (60 V DC, Ãâ = 40 ms, N/C contact: 6 W) 35 W (110 V DC, Ãâ = 40 ms, N/C contact: 11 W) 48 W (220 V DC, Ãâ = 40 ms, N/C contact: 22 W) Switching capacity: min. 75 mW Switching capacity (3600/h cycles): 5 A (24ÃV (DC13)) 5 A (230 V (AC15)) Output fuse: 10 A gL/gG (N/O contact) 4 A gL/gG (for low-demand applications) 150 mA Fast-blow (N/C contact) |
Connection data | Connection technology pluggable: yes Conductor connection Connection method: Screw connection Conductor cross section rigid: 0.2 mm² ... 2.5 mm² Conductor cross section flexible: 0.2 mm² ... 2.5 mm² Conductor cross-section AWG: 24 ... 12 Stripping length: 7 mm Screw thread: M3 |
Dimensions | Width: 17.5 mm Height: 99 mm Depth: 114.5 mm |
Material specifications | Housing material: Polyamide |
Characteristics | Safety data Stop category: 0 Safety data: ENÃISOÃ13849 Category: 1 (Diagnostic coverage (DC) of the control unit at A1/A2 must be ââ°¥Ã90Ã%) Performance level (PL): c (Diagnostic coverage (DC) of the control unit at A1/A2 must be ââ°¥Ã90Ã%) Safety data: ENÃ50156 Safety Integrity Level (SIL): 2 Safety data: IEC 61508 - High demand Safety Integrity Level (SIL): 2 (max.Ã10%Ãof the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ââ°¥Ã90%Ã) Safety data: IEC 61508 - Low demand Safety Integrity Level (SIL): 2 (max.Ã10%Ãof the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ââ°¥Ã90%Ã) Safety data: ENÃIEC 62061 Safety Integrity Level (SIL): 1 (max.Ã10%Ãof the entire SIL; diagnostic coverage (DC) of the control unit at A1/A2 must be ââ°¥Ã90%Ã) |
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Min. degree of protection of inst. location: IP54 Ambient temperature (operation): -20°C ... 55°C (observe derating) Ambient temperature (storage/transport): -40°C ... 70°C Maximum altitude: ââ°¤ 2000 m (Above sea level) Max. permissible humidity (storage/transport): 75 % (on average, 85% infrequently, non-condensing) Max. permissible relative humidity (operation): 75 % (on average, 85% infrequently, non-condensing) Shock: 15g Vibration (operation): 10ÃHzÃ...Ã150ÃHz, 2g |
Approvals | CE Certificate: CE-compliant |
Standards and regulations | Air clearances and creepage distances between the power circuits Standards/regulations: IEC 60664-1 |
Mounting | Mounting type: DIN rail mounting Mounting position: any Connection method: Screw connection |
Description other products