PHOENIX CONTACT 2903151
PHOENIX CONTACTNon disponibile

TRIO-PS-2G/1AC/24DC/20 - Power supply unit

Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: single-phase, output: 24VDC/20A
Cod. Articolo: 2903151
Cod. Fornitore: 2903151
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Specifiche
Download
Caratteristiche Tecniche
Input dataAC operation
Network type: Star network
Nominal input voltage range: 100 VAC ... 240 VAC
Input voltage range: 100 VAC ... 240 VAC -15%...+10%
Electric strength, max.: ≤ 300 VAC 15 s
Typical national grid voltage: 120 VAC
230 VAC
Voltage type of supply voltage: AC/DC
Inrush current: ≤ 20 A (typical)
Inrush current integral (I2t): < 0.9 A2s
Inrush current limitation: typ. 20 A (after 1ms)
AC frequency range: 50 Hz ... 60 Hz ±10%
Mains buffering time: typ. 10 ms (120VAC)
typ. 15 ms (230 V AC)
Current consumption: 5.6 A (100VAC)
4.3 A (120VAC)
2.4 A (230 V AC)
2.4 A (240VAC)
Nominal power consumption: 534.7 VA
Protective circuit: Transient surge protection; Varistor
Power factor (cos phi): 0.98
Typical response time: < 1 s
Input fuse: 10 A (internal (device protection))
Recommended breaker for input protection: 10 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE: < 3.5 mA
POWER factor: > 0.9 (120VAC)
> 0.9 (230 V AC)
DC operation
Nominal input voltage range: 110 VDC ... 250 VDC
Input voltage range: 110 VDC ... 250 VDC ±10%
Extended input voltage range in operation: > 99 VDC
Switch-on voltage: ≥ 96 VDC
Shut-down voltage: < 95 VDC
Mains buffering time: > 15 ms (230 V AC)
Current consumption: 4.9 A (110VDC)
2.1 A (250VDC)
Output dataEfficiency: typ. 91.4 % (120VAC)
typ. 92.9 % (230 V AC)
Output characteristic: U/I with dynamic load reserve
Nominal output voltage: 24 VDC ±1%
Setting range of the output voltage (USet): 24 VDC ... 28 VDC (> 24 VDC, constant capacity restricted)
Nominal output current (IN): 20 A
Dynamic Boost (IDyn.Boost): 30 A (5 s)
Derating: > 60°C ... 70°C (2.5%/K)
POWER factor: > 0.9 (120VAC)
> 0.9 (230 V AC)
Feedback voltage resistance: ≤ 35 VDC
Protection against overvoltage at the output (OVP): ≤ 30 VDC
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 100 mVPP (with nominal values)
Short-circuit-proof: yes
No-load proof: yes
Output power: 480 W
720 W
Maximum no-load power dissipation: < 2.9 W (120VAC)
< 2.8 W (230 V AC)
Power loss nominal load max.: < 44.8 W (120VAC)
< 36.8 W (230 V AC)
Rise time: 20 ms (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK
Continuous load current: 100 mA
Signal relay 13/14
Default: closed
Digital: 30 VAC 30 VDC 100 mA
Connection dataInput
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 4 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 10 mm
Output
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 10 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 6 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 6 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 8
Stripping length: 15 mm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 1.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 1.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 16
Stripping length: 8 mm
SignalingTypes of signaling: LED
Floating signal contact
Signal output: LED status indicator
Signalization designation: DC OK
Status display: LED
Color: green
DC OK: UOUT > 0.9 x UN (UN = 24VDC)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 3 kV AC (type test)
1.5 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: TRIO POWER
MTBF (IEC 61709, SN 29500): > 1800000 h (25°C)
> 1000000 h (40°C)
> 480000 h (60°C)
Insulation characteristics
Protection class: I (in closed control cabinet)
Degree of pollution: 2
DimensionsWidth: 68 mm
Height: 130 mm
Depth: 160 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: horizontally 0 mm (≤ 40°C) 10 mm (≤ 70°C), vertically 50 mm
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsFlammability rating according to UL94 (housing / terminal blocks): V0
Housing material: Metal
Type of housing: Aluminum (AlMg3)
Hood version: Polycarbonate
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>60°C Derating: 2,5%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 4000 m (>2000m, Derating: 10%/1000m)
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 4g, 90 min.
Standards and regulationsRail applications: EN50121-4
Standard – Electronic equipment for use in electrical power installations and their assembly into electrical power installations: EN50178/VDE0160 (PELV)
Standard – Limitation of mains harmonic currents: EN61000-3-2
Standard - Electrical safety: IEC 60950-1/VDE0805 (SELV)
Standard – Safety extra-low voltage: IEC 60950-1 (SELV) and EN60204-1 (PELV)
Standard - Safe isolation: DINVDE0100-410
Standard - Safety of transformers: EN61558-2-16 (air clearances and creepage distances only)
ApprovalsShipbuilding approval: DNV GL
UL approvals: UL Listed UL508
UL/C-UL Recognized UL60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
Conformity/Approvals
SIL in accordance with IEC 61508: 0
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN61000-6-3
EN61000-6-4
EMC requirements for noise immunity: EN61000-6-1
EN61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Conducted noise emission: EN55016
EN61000-6-3 (Class B)
Noise emission: EN 55011 (EN 55022)
EN55016
EN61000-6-3 (Class B)
Harmonic currents
Frequency range: Class A, B
Flicker
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN61000-4-2
Electrostatic discharge​
Contact discharge: 6 kV (Test Level 4)
Discharge in air: 8 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN61000-4-3
Electromagnetic HF field​
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN61000-4-4
Fast transients (burst)​
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN61000-4-5
Input: 3 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 1 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: EN61000-4-6
Conducted interference​
Input/Output: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Emitted interference
Standards/regulations: EN61000-6-3
Radio interference voltage in acc. with EN 55011: EN55011 (EN55022) ClassB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Specifiche
ECLASSECLASS-11.0: 27040701
ECLASS-13.0: 27040701
ECLASS-12.0: 27040701
ETIMETIM 9.0: EC002540
UNSPSCUNSPSC 21.0: 39121000
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00041.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01301.pdf

Data_sheet_03802.pdf

Manufacturer_declaration_03079.pdf

Manufacturer_declaration_04783.pdf

Manufacturer_declaration_05508.pdf

Manufacturer_declaration_15778.pdf

Package_slip_02446.pdf

Technical_drawing_39710.pdf

Various_00006.pdf