Industrial Automation
AXL F SSI1 AO1 1H - Special function module


Dimensions | Dimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/70f8cf974520554e81de80f4005f2af3/-S204x204-FJPG Width: 35 mm Height: 126.1 mm Depth: 54 mm Note on dimensions: The depth applies when a THÃ35-7.5 DIN rail is used (in accordance with ENÃ60715). |
Interfaces | AxiolineÃFÃlocal bus Number of interfaces: 2 Connection method: Bus base module Transmission speed: 100 Mbps |
System properties | Module ID code (hex): none Input address area: 12 Byte Output address area: 12 Byte Required parameter data: 29 Byte Required configuration data: 7 Byte |
Input data | Encoder Number of inputs: 1 Input name: SSI interface Description of the input: RS-422 interface in accordance with SSI specification Encoder signals: Single-turn and multi-turn encoder, length measuring sticks Input frequency: to 2 MHz (Can be parameterized: 62.5ÃkHz, 125ÃkHz (default), 250ÃkHz, 500ÃkHz, 1ÃMHz, 2ÃMHz) Parity: Even, odd or no parity Transmission frequency: 2 MHz Adjustable resolution: 8 ... 56 bit Encoder supply voltage: 24 VÃDC (UI - 0.5ÃV) |
Output data | Analog Output name: Analog outputs Connection method: Push-in connection Connection technology: 2-conductor (shielded, twisted pair) Number of outputs: 1 D/A conversion time: 5 õs D/A converter resolution: 16 bit Protective circuit: Surge protection; Electronic (35ÃV, permanent) Short-circuit and overload protection; Electronic Transient protection; Suppressor diode Data formats: IB IL, S7-compatible, standardized representation Measured value representation: 16 bits Representation of output values: 16 bits (15 bits + sign) Current output signal: 0 mA ... 20 mA 4 mA ... 20 mA -20 mA ... 20 mA Load/output load current output: max. 500 é Voltage output signal: 0 V ... 5 V -5 V ... 5 V 0 V ... 10 V -10 V ... 10 V Load/output load voltage output: > 2 ké Permissible cable length: max. 250 m |
Product properties | Type: block modular Product type: I/O component Product family: AxiolineÃF Mounting position: any (no temperature derating) Scope of delivery: including bus base module and AxiolineÃF connectors Insulation characteristics Overvoltage category: II (IEC 60664-1, ENÃ60664-1) Pollution degree: 2 (IEC 60664-1, ENÃ60664-1) |
Electrical properties | Encoder Nominal output voltage: 24 VÃDC (UI - 0.5ÃV) Voltage range: 19.5 VÃDC ... 30 VÃDC (including all tolerances, including ripple) Current carrying capacity: max. 500 mA Protective circuit: Surge protection; electronic (35 V, 0.5 s) Short-circuit/overload protection; Electronic Transient protection; Shielding Potentials: AxiolineÃF local bus supply (U Supply voltage: 5 VÃDC (via bus base module) Current draw: max. 140 mA Power consumption: max. 0.7 W Potentials: Feed-in of supply voltage (U Supply voltage: 24 VÃDC Supply voltage range: 19.2 VÃDC ... 30 VÃDC including all tolerances, including ripple Current draw: max. 60 mA (Supply of the SSI interface and the analog output (20ÃmA), without sensor supply) Power consumption: max. 1.4 W (Supply of the SSI interface and the analog output (20ÃmA), without sensor supply) Protective circuit: Surge protection; electronic (35 V, 0.5 s) Reverse polarity protection; Polarity protection diode Transient protection; Suppressor diode Electrical isolation/isolation of the voltage ranges Test voltage: Logic: 500 VÃAC, 50 Hz, 1 min. Test voltage: SSI I/O (24 V supply): 500 VÃAC, 50 Hz, 1 min. Test voltage: Functional ground: 500 VÃAC, 50 Hz, 1 min. Test voltage: Analog I/O: 500 VÃAC, 50 Hz, 1 min. |
Connection data | Connection technology Connection name: AxiolineÃF connector Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor connection Connection method: Push-in connection Conductor cross section rigid: 0.2 mm² ... 1.5 mm² Conductor cross section flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm AxiolineÃF connector Connection method: Push-in connection Note on the connection method: Please observe the information provided on conductor cross sections in the ââ¬Ã AxiolineÃF: system and installationâ⬠user manual. Conductor cross section, rigid: 0.2 mm² ... 1.5 mm² Conductor cross section, flexible: 0.2 mm² ... 1.5 mm² Conductor cross section AWG: 24 ... 16 Stripping length: 8 mm |
Environmental and real-life conditions | Ambient conditions Ambient temperature (operation): -25°C ... 60°C Degree of protection: IP20 Air pressure (operation): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Air pressure (storage/transport): 70 kPa ... 106 kPa (up to 3000Ãm above sea level) Ambient temperature (storage/transport): -40°C ... 85°C Permissible humidity (operation): 5 % ... 95 % (non-condensing) Permissible humidity (storage/transport): 5 % ... 95 % (non-condensing) |
Standards and regulations | Protection class: III (IEC 61140, ENÃ61140, VDEÃ0140-1) |
Mounting | Mounting type: DIN rail mounting Mounting position: any (no temperature derating) |